Chapter 2
Install the Dynamix 1444 Series Monitoring System
34

Wiring Requirements

WARNING: All wiring must comply with applicable electrical installation
requirements (for example, N.E.C. article 501-4(b)).
All modules (whether main or Expansion) have four removable connectors
where the field wiring is made. They come in a choice of spring cage or screw
connection. Both types benefit from the following:
• Screwdriver axis parallel to conductor axis
• Positive connector retention (captive screws)
• Test connections for 1.2 mm (0.047 in.) diameter test pins or 1 mm
(0.039 in.) test plugs
The DYN module connectors are 16 way and the expansion module
connectors are 6 way. Each is keyed appropriate to location and module type.
Manufacturer technical data for these connectors is as follows.
Attribute
Tightening torque, min- max (screw type only)
Normal cross-section
Stripping length
Conductor cross-section solid or stranded min- max
Conductor cross-section stranded with ferrule without
plastic sleeve min- max
Conductor cross-section stranded with ferrule with plastic
sleeve min- max
Conductor cross-section AWG/kcmil min- max - screw
clamp type
Conductor cross-section AWG/kcmil min- max - spring
clamp type
AWG according to ULL/CUL min- max -screw clamp type
AWG according to ULL/CUL min- max -spring clamp type
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Value
0.22...0.25 N•m (0.16...0.18 ft·lbf)
2
1.5 mm
(0.002 in2)
9 mm (0.35 in)
2
0.14...1.5 mm
(0.0002...0.002 in2)
2
0.25...1.5 mm
(0.0003...0.002 in2)
2
0.25...0.5 mm
(0.0003...0.0007 in2)
2
28...16 mm
2
26...16 mm
2
30...16 mm
2
28...16 mm