Allen-Bradley 1444-TSCX02-02RB User Manual page 116

Monitoring system
Table of Contents

Advertisement

Chapter 3
Configure the 1444 Dynamic Measurement Module
Proportional DC
Transmitter Temperature °F
Transmitter Temperature °C
Transmitter Temperature °K
DC Current
DC Voltage
Position
Accelerometer Temperature °F
Accelerometer Temperature °C
Accelerometer Temperature °K
Eccentricity
Channel Type
Dynamic (AC)
Input Tag
Measurement Type Selections
Shaft Absolute pk-pk
Shaft Relative (LP/HP filtered)
116
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Proportional voltage measurements.
Common thrust/axial position measurement. Measures the offset and
direction of movement.
Proportional voltage measurements.
The measurement of shaft bow (the shaft peak to peak displacement) at
slow roll speed by either of two methods (with or without a speed
input).
Comment
Calculates the peak to peak shaft absolute radial displacement
measured from the sum of:
A shaft to case relative displacement (eddy current probe)
measurement, and
A case absolute displacement measurement from an integrated velocity
transducer or double integrated accelerometer that is mounted in-line
with the eddy current probe.
The first channel of the pair must be the accelerometer or velocity sensor
and its Measurement Type must be one of:
absolute vibration (A to D)
absolute vibration (AV to D)
absolute vibration (V to D)
The second channel of the pair must be the displacement sensor and its
Measurement Type set to Shaft Relative (LP/HP).

Hide quick links:

Advertisement

Table of Contents
loading