Table 36 - Configurable Parameters for Rod Drop Measurements
Parameters
Values
Units
Select from presented
displacement units
Time Constant
0.1...60.0 seconds
Calibration Units
EU (0)
Volts (1)
Calibration Offset
-50,000...50,000
Tachometer
0 (Tacho/Speed 0)
1 (Tacho/Speed 1)
In
Table
35, the maximum RPM values available for each Angular Range
selection are presented.
Table 35 - Maximum RPM for Angular Range
Angular Range
Max RPM
2
976
4
1953
6
2929
8
3905
10
4882
12
5858
14
6834
16
7811
18
8787
20
9763
Configuring Rod Drop Measurements
Rod drop measurements are configured using the controls in
Figure 65 - Rod Drop Measurements
Comments
Rod drop measurements are made using eddy current probes. Configuration of the units, time constant, calibration
offset, and sense control are the same as for
Select the source for the tachometer that is used in the rod drop measurement.
Value that is written to the assembly is 1 or 2, 0 = off (to the module).
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Measurement Definition
Normal Thrust
measurements.
Chapter 4
Figure
65.