Alarm Status Structure - Allen-Bradley 1444-TSCX02-02RB User Manual

Monitoring system
Table of Contents

Advertisement

Tag (continued)
ExpTachSpeed0Uncertain
Tachometer Signal Conditioner Speed 0 Uncertain
ExpTachSpeed1Uncertain
Tachometer Signal Conditioner Speed1 Uncertain
ExpTachInput0Fault
Tachometer Signal Conditioner Speed 0 Fault
ExpTachInput1Fault
Tachometer Signal Conditioner Speed 1 Fault
Description (if = 1)
Speed 0/1 is less than previous measured. Reported speed is estimated until a further pulse is detected,
or until zero speed is determined (maximum pulse wait time exceeded).
Tacho sensor fault. Indicates bias out of range and/or speed out of range and/or TSCX module fault.

Alarm Status Structure

The alarm status structure consists of an array of 13 records
present the status of associated voted alarms.
If Alarm Status Alignment is Dynamic, then status records are also assigned to
relays that are configured to act only on fault, and to any unused (not enabled)
relays.
See
Alarm System Overview on page 211
page 212
for further information on how Alarm Statuses are associated with
Voted Alarms and Relays.
Module status excludes an assembly for each measurement alarm. The status of
a measurement alarm that is referenced by a voted alarm is included in the
alarm status record that is associated with the voted alarm.
DINT
AlarmStatus[13]
The status structure consists of the parameters that are shown in
Alarm Status to Relay and Voted Alarm Association
How Alarm Statuses
(Figure
relays varies with the selected method of alignment. (See
The two methods of aligning the Alarm Status, Dynamic (default) and Static,
are described in
Alarm Status Alignment on page
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Operate the Module
and
Alarm Status Alignment on
94) are allocated and assigned to voted alarms and
212, and in this section.
Chapter 10
(Table
67) that
Table
68.
Table 15 on page
98).
277