Dynamix Transducer Object

Table 146 - Instance Attributes
Attribute ID
Access Rule NV
1
Get
V
2
Get
V
Transducer Descriptions
16
Get
V
17
Get
V
18
Get
V
19
Get
V
Transducer Output Definition
24
Get
V
25
Get
V
26
Get
V
The transducer object (class code 0x38E)defines the properties of the sensor
that is connected to one of the four available physical inputs.
Attributes describe physical measurement parameters and transducer OK
monitoring setup, as also some sensor-mounting geometry settings.
This object reports transducer DC Volts (bias) measurement and transducer
status.
Table 144 - Object Instances
Instance ID
0
Table 145 - Class Attributes
Attribute
Access
ID
Rule
1
Get
8
Get
Name
Data Type
DC Bias
REAL
TX Detailed Status
BYTE
Group of four attributes that are used for reference purposes only.
Transducer Name
SINT[32]
Transducer Orientation
INT
Transducer Location
SINT
Transducer Output Sense
SINT
Group of five configuration attributes.
Transducer AC Units
ENGUNITS
Transducer AC Sensitivity
REAL
Transducer DC Units
ENGUNITS
Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Description
Transducer Class Instance
NV
Name
Data
Type
NV
Revision
UINT
V
TX Overall Status
BYTE
Description of Attribute
The DC level at the input in fixed
units of DC Volts.
Detailed bit-coded Transducer
Status (Data).
Descriptive name.
Definition of sensor orientation
angle in degrees. Orientation
angle is usually a radial angular
orientation.
Transducer location definition.
Sensor output sense - information
only. The DC measurement object
has normal/counter control.
Transducer measurement units
that are used for AC measurement
base.
TX AC Sensitivity in mV/TX AC
units.
Transducer measurement units
that are used for DC measurement
base.
CIP Objects
Description of
Semantics of Values
Attribute
Current object revision.
Current revision.
Coded information to
Bits 0...3 represent
represent transducer
transducer
Enabled and OK status
enabled status (1 =
enabled).
Bits 4...7 represent
transducer OK status (1
= OK).
Semantics of Values
Data
See TX OK Configuration Decoding
32 characters
0...359 degree input range in
increments of 1 °
0: Unknown
1: Radial
2: Axial
Fixed at zero
Supported engineering units
Range: 1...20000
Supported engineering units