Using Message Instructions; Processing Real-Time Control And Module Services; One Service Performed Per Instruction - Allen-Bradley 1756-CFM User Manual

Controllogix configurable flowmeter module
Table of Contents

Advertisement

Using Message Instructions

Ladder logic uses message instructions to change the module configuration
during module operation.
Message instructions maintain these characteristics:
messages use unscheduled portions of system communication
bandwidth
one service is performed per instruction
performing module services does not impede module functionality, such
as counting incoming pulses

Processing Real-Time Control and Module Services

Because message instructions use unscheduled portions of systems
communication bandwidth, the services requested of a module are not
guaranteed to occur within a specific time period. Although the module
response typically occurs in less than a second, there is no specific time
interval that reflects this response.

One Service Performed Per Instruction

Message instructions only cause a module service to be performed once per
execution. For example, if a message instruction sends new configuration data
to the module, the message instruction must be reexecuted to update send the
configuration data in the future.
Rockwell Automation Publication 1756-UM010C-EN-P - June 2021
Chapter 5
Configure the Configurable Flowmeter Module
81