How To Enable Output Behavior Configuration

To enable output behavior configuration for a 1756-CFM module with
firmware revision 2.4, select one of these options.
If you are using RSLogix 5000® software version 16 or earlier, see
page
129.
If you are using programming software version 17 or later, add a new
module to your I/O Configuration folder and complete these steps.
1. On the Select Module screen, select the 1756-CFM module and click OK.
The Select Major Revision window opens.
2. Verify that Major Revision 2 is chosen and click OK.
The New Module dialog box opens with Major Revision 2 chosen.
Output Behavior configuration is enabled.
Rockwell Automation Publication 1756-UM010C-EN-P - June 2021
Chapter 3
Configurable Flowmeter Module Features and Operational Modes
53