Mitsubishi Electric MELSEC iQ-R16MTCPU Programming Manual page 411

Melsec iq-r series motion controller
Hide thumbs Also See for MELSEC iQ-R16MTCPU:
Table of Contents

Advertisement

Error
Error name
code
3A64H
16-bit batch Mn read error
3A65H
32-bit batch Mn read error
3A66H
16-bit batch Bn read error
3A67H
32-bit batch Bn read error
3A68H
16-bit batch Fn read error
3A69H
32-bit batch Fn read error
3A6AH
16-bit batch SMn read
error
3A6BH
32-bit batch SMn read
error
3A6CH
16-bit batch X(n) read
error
3A6DH
32-bit batch X(n) read
error
3A6EH
16-bit batch Y(n) read
error
3A6FH
32-bit batch Y(n) read
error
3A70H
16-bit batch M(n) read
error
Error details and cause
The directly specified device No. is outside the range.
The directly specified device No. is outside the range.
The directly specified device No. is outside the range.
• The directly specified device No. is outside the range.
The directly specified device No. is outside the range.
The directly specified device No. is outside the range.
The directly specified device No. is outside the range.
The directly specified device No. is outside the range.
The indirectly specified device No. is outside the range or
is not a multiple of 16.
The indirectly specified device No. is outside the range or
is not a multiple of 16.
The indirectly specified device No. is outside the range or
is not a multiple of 16.
The indirectly specified device No. is outside the range or
is not a multiple of 16.
The indirectly specified device No. is outside the range or
is not a multiple of 16.
Corrective action
• Correct the program so that the device No. which
directly specifies is proper.
• Set the device range according to the device number/
latch setting of relation setting of CPU parameter within
the valid range.
• Correct the program so that the device No. which
directly specifies is proper.
• Set the device range according to the device number/
latch setting of relation setting of CPU parameter within
the valid range.
• Correct the program so that the device No. which
directly specifies is proper.
• Set the device range according to the device number/
latch setting of relation setting of CPU parameter within
the valid range.
• Correct the program so that the device No. which
directly specifies is proper.
• Set the device range according to the device number/
latch setting of relation setting of CPU parameter within
the valid range.
• Correct the program so that the device No. which
directly specifies is proper.
• Set the device range according to the device number/
latch setting of relation setting of CPU parameter within
the valid range.
• Correct the program so that the device No. which
directly specifies is proper.
• Set the device range according to the device number/
latch setting of relation setting of CPU parameter within
the valid range.
• Correct the program so that the device No. which
directly specifies is proper.
• Set the device range according to the device number/
latch setting of relation setting of CPU parameter within
the valid range.
• Correct the program so that the device No. which
directly specifies is proper.
• Set the device range according to the device number/
latch setting of relation setting of CPU parameter within
the valid range.
• Correct the program so that the device No. which
indirectly specifies is proper.
• Set the device range according to the device number/
latch setting of relation setting of CPU parameter within
the valid range.
• Correct the program so that the device No. which
indirectly specifies is proper.
• Set the device range according to the device number/
latch setting of relation setting of CPU parameter within
the valid range.
• Correct the program so that the device No. which
indirectly specifies is proper.
• Set the device range according to the device number/
latch setting of relation setting of CPU parameter within
the valid range.
• Correct the program so that the device No. which
indirectly specifies is proper.
• Set the device range according to the device number/
latch setting of relation setting of CPU parameter within
the valid range.
• Correct the program so that the device No. which
indirectly specifies is proper.
• Set the device range according to the device number/
latch setting of relation setting of CPU parameter within
the valid range.
APPENDICES
Appendix 1 Error Codes
A
409