*1
Item
Application
Scaling function
Scaling enable/disable setting
setting
Scaling range upper limit value
Scaling range lower limit value
Scaling width upper limit value
Scaling width lower limit value
Warning output
Warning output setting (Process
function
alarm)
(Process alarm)
Process alarm upper upper limit
value
Process alarm upper lower limit
value
Process alarm lower upper limit
value
Process alarm lower lower limit
value
Warning output
Warning output setting (Rate
function (Rate
alarm)
alarm)
Rate alarm detection cycle
setting
Rate alarm upper limit value
Rate alarm lower limit value
Disconnection
Disconnection detection
detection
function enable/disable setting
function
Conversion setting for
disconnection detection
Conversion setting value for
disconnection detection
Disconnection detection
automatic clear enable/disable
setting
Logging function
Logging enable/disable setting
Logging data setting
Logging cycle setting value
Logging cycle unit setting
Level trigger condition setting
Logging points after trigger
Trigger data
Trigger setting value
Logging loading enable/disable
setting
Logging read points setting
value
Online module
Auto restore of Offset/gain
change
setting with the module change
Interrupt
Condition target setting
setting
Condition target channel setting
Interrupt factor transaction setting
Interrupt pointer
*1 Items that can be set will differ depending on the module used.
*2 Setting range will differ depending on the module used.
*2
Setting range
Enable/Disable
-3276.8 to -0.1, 0.1 to 3276.7
-3276.8 to -0.1, 0.1 to 3276.7
-32768 to -1, 1 to 32767
-32768 to -1, 1 to 32767
Enable/Disable
-270.0 to 1820
-270.0 to 1820
-270.0 to 1820
-270.0 to 1820
Enable/Disable
1 to 32000 times
0.1 to 3276.7
-3276.8 to -0.1
Enable/Disable
Up scale/Down scale/Given value/Value immediately
before disconnection
-3276.8 to 3276.7
Enable/Disable
Enable/Disable
Measured temperature value/Scaling value
ms: 10 to 32767
s: 1 to 3600
ms/s
Disable/Level trigger (Condition: Rise)/Level trigger
(Condition: Fall)/Level trigger (Condition: Rise and Fall)
1 to 1000
0 to 9999
-32768 to 32767
Enable/Disable
1 to 1000
Enable/Disable
Disable/Error flag/Warning output flag (Process alarm)/
Warning output flag (Rate alarm)/Disconnection detection
flag/Conversion completed flag/Logging hold flag/Logging
read
All CH specification/CH1/CH2/CH3/CH4/CH5/CH6/CH7/
CH8
Interrupt reissue requests/No Interrupt reissue requests
I0 to I15
Default value
Disable
Disable
Disable
Enable
Down scale
Disable
Disable
Enable
Disable
All CH specification
Interrupt reissue requests