Mitsubishi Electric MELSEC iQ-R16MTCPU Programming Manual page 30

Melsec iq-r series motion controller
Hide thumbs Also See for MELSEC iQ-R16MTCPU:
Table of Contents

Advertisement

■Temperature input module
*1
Item
Basic
RTD type
setting
selection
function
Thermocouple
type selection
function
Cold junction
temperature
compensation
with/without
setting function
Operation mode
setting function
Conversion
enable/disable
setting function
Temperature
conversion
system
1 MULTIPLE CPU SYSTEM
28
1.1 Multiple CPU System
RTD type setting
Offset/gain setting
Thermocouple type setting
Offset/gain setting
Cold junction temperature
compensation with/without
setting
Operation mode setting
Conversion enable/disable
setting
Average processing setting
Time average/Count average/
Moving average/Primary delay
filter constant setting
*2
Setting range
Pt100(-200 to 850)/Pt100(-20 to 120)/JPt100(-180 to
600)/JPt100(-20 to 120)/Pt100(0 to 200)/JPt100(0
to 200)/Ni100(-60 to 250)/Pt50(-200 to 650)
Factory default setting/User range setting
Thermocouple K/Thermocouple E/Thermocouple J/
Thermocouple T/Thermocouple B/Thermocouple R/
Thermocouple S/Thermocouple N
Factory default setting/User range setting
With cold junction temperature compensation/Without cold
junction temperature compensation
Normal mode (conversion process)/Offset/gain setting
mode
Conversion enable/Conversion disable
Sampling processing/Time average/Count average/Moving
average/ Primary delay filter
Time average: 40 to 5000ms
Count average: 4 to 500 times
Moving average: 2 to 200 times
Primary delay filter: 1 to 500 times
Default value
Pt100(-200 to 850)
Factory default setting
Thermocouple K
Factory default setting
With cold junction
temperature compensation
Normal mode (conversion
process)
Conversion disable
Sampling processing

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-r32mtcpu melsec iq-r64mtcpu

Table of Contents