Mapping Input Power From Ac Power Distribution Modules To Ac Power Supply Modules On The Mx2020 Router; Table 63: Calculating Ac Thermal Output - Juniper MX2020 Hardware Manual

3d universal edge router
Hide thumbs Also See for MX2020:
Table of Contents

Advertisement

MX2020 3D Universal Edge Router Hardware Guide
Related
Documentation
Mapping Input Power from AC Power Distribution Modules to AC Power Supply Modules
on the MX2020 Router
168

Table 63: Calculating AC Thermal Output

Power Distribution Module
MX2020 Three-phase delta AC PDM
MX2020 Three-phase wye AC PDM
MX2020 Power Subsystem Description on page 83
MX2020 AC Power Requirements on page 147
Connecting AC Power to an MX2020 Router with Three-Phase Delta AC Power
Distribution Modules on page 249
Connecting AC Power to an MX2020 Router with Three-Phase Wye AC Power
Distribution Modules on page 252
MX2020 AC Power Subsystem Electrical Specifications on page 158
MX2020 AC Power Cord Specifications on page 154
MX2020 AC Power Electrical Safety Guidelines on page 584
You connect AC power to the router with AC PDMs by connecting two AC power cords
to each PDM. One feed maps to six PSMs and the other maps to three PSMs (see
Figure 74 on page
169). The arrangement matches the internal components of the PDM.
Table 64 on page 169
shows the AC PDM input mapping to AC
PDM1/Input1
.
Table 65 on page 170
and
.
PDM3/Input1
Thermal Output (BTUs per hour)
Maximum power divided by 0.91 * 3.41 = BTU/hr.
Input power = Maximum power divided by 0.91
Refer to
"MX2020 AC Power Requirements" on
page 147
to calculate maximum power, which is
dependent on configuration and temperature.
Maximum power divided by 0.91 * 3.41 = BTU/hr.
Input power = Maximum power divided by 0.91
Refer to
"MX2020 AC Power Requirements" on
page 147
to calculate maximum power, which is
dependent on configuration and temperature.
shows the AC PDM input mapping to AC
Copyright © 2015, Juniper Networks, Inc.
and
PDM0/Input0
PDM2/Input0

Advertisement

Table of Contents
loading