Figure 65: Three-Phase Delta AC Power Cord Mating Connector

Figure 66: Three-Phase Wye AC Power Cord Mating Connector

NOTE:
In North America, AC power cords must not exceed 4.5 m
(approximately 14.75 ft) in length, to comply with National Electrical Code
(NEC) Sections 400-8 (NFPA 75, 5-2.2) and 210-52, and Canadian Electrical
Code (CEC) Section 4-010(3). The cords supplied with the router are in
compliance.
CAUTION:
The router is pluggable type A equipment installed in a
restricted-access location. It has a separate protective earthing terminal (size
for UNC 1/4-20 ground lugs) provided on the chassis in addition to the
grounding pin on the power cord. This separate protective earthing terminal
must be permanently connected to earth.
CAUTION:
Power cords and cable must not block access to device
components or drape where people could trip on them.
Connecting AC Power to an MX2020 Router with Three-Phase Delta AC Power
Distribution Modules on page 249
Chapter 13: AC Power Requirements, Specifications, and Guidelines
157