Maintaining The Mx2020 Power Usage - Juniper MX2020 Hardware Manual

3d universal edge router
Hide thumbs Also See for MX2020:
Table of Contents

Advertisement

Related
Documentation

Maintaining the MX2020 Power Usage

Purpose
Action
Copyright © 2015, Juniper Networks, Inc.
DC Output
Hours Used
Make sure that the power and grounding cables are arranged so that they do not
obstruct access to other router components.
Routinely check the status LEDs on the AC or DC PSM faceplates and the craft interface
to determine if the PSMs are functioning normally.
Check the red and yellow alarm LEDs on the craft interface. PSM failure or removal
triggers an alarm that causes one or both of the LEDs to light. You can display the
associated error messages by issuing the following command:
user@host> show chassis alarms
Periodically inspect the site to ensure that the grounding and power cables connected
to the router are securely in place and that there is no moisture accumulating near the
router.
MX2020 Power Subsystem Description on page 83
MX2020 Troubleshooting Resources on page 531
Troubleshooting the MX2020 Power Subsystem on page 541
Overview of Preparing the Site for the MX2020 Router on page 103
For optimum router performance, verify the AC or DC power usage.
On a regular basis:
Make sure that the total system power consumption and capacity doesn't exceed the
maximum allocated.
Issue the
show chassis power
DC power system.
The output displays the AC chassis power for 2100 W capacity.
user@host>show chassis power
PSM 0:
State:
Online
AC input:
OK (INP0 feed expected, INP0 feed connected)
Capacity:
2100 W (maximum 2100 W)
DC output: 271.69 W (Lower Zone, 5.25 A at 51.75 V, 12.94% of capacity)
PSM 1:
State:
Online
AC input:
OK (INP0 feed expected, INP0 feed connected)
Capacity:
2100 W (maximum 2100 W)
DC output: 247.00 W (Lower Zone, 4.75 A at 52.00 V, 11.76% of capacity)
PSM 2:
State:
Online
Chapter 23: Maintaining Components
INP1
51.60
Voltage(V) Current(A)
Power(W)
51.25
9.25
2970
command to display the information about the AC or
10.15
523.74
Load(%)
474.06
22.57
391