Figure 76: 4-Awg Dc Power Cable Lug; Figure 77: 6-Awg Dc Power Cable Lug; Table 73: Dc Power Cable Specifications - Juniper MX2020 Hardware Manual

3d universal edge router
Hide thumbs Also See for MX2020:
Table of Contents

Advertisement

Copyright © 2015, Juniper Networks, Inc.

Figure 76: 4-AWG DC Power Cable Lug

End view
0.27
0.55
2 holes
0.09
0.25
0.63

Figure 77: 6-AWG DC Power Cable Lug

End view
.48 ±.04
.25 ±.04
CAUTION:
Before router installation begins, a licensed electrician must attach
a cable lug to the grounding and power cables that you supply. A cable with
an incorrectly attached lug can damage the router.
CAUTION:
The router is a pluggable type A equipment installed in restricted
access location. It has a separate protective earthing terminal (Metric [–M6]
and English [–¼-20] screw ground lugs) provided on the chassis in addition
to the grounding pin of the power supply cord. This separate protective earth
terminal must be permanently connected to earth.
Table 73 on page 185
summarizes the specifications for the power cables, which you must
supply.

Table 73: DC Power Cable Specifications

Cable Type
Quantity and Specification
Power
Eighteen pairs of 4-AWG (21.2 mm
wire, or as required by the local code
Power
Eighteen pairs of 6-AWG (13.3 mm
wire, or as required by the local code
Chapter 14: DC Power Requirements, Specifications, and Guidelines
Inner diameter .28
All measurements in inches
Inner diameter .22
0.63 ±.02
.27 ±.02
2 PLC
All measurements in inches
2
), used with 80-A PDM. Minimum 90°C
2
), used with 60-A PDM. Minimum 90°C
185