9424200994 Rev U
Setting
Mode
Voltage Difference
Slip Angle
Slip Frequency
Source Freq > Destination Freq
Angle Compensation
25 VM Live Voltage
25 VM Dead Voltage
25 VM Drop Out Delay
25 Voltage Monitor Logic
BE1-11g
Figure 43. Sync-Check Settings Screen
Table 13. Operational Settings
Range
Disabled or Enabled
0 or 1 to 50
1 to 99
0.01 to 0.5
Disabled or Enabled
0 to 359.9
0 or 10 to 90
0 or 10 to 90
0 or 50 to 60,000
0 = Disabled
123, 12, 13, 23
Increment
Unit of Measure
n/a
n/a
1
percent
1
degrees
0.01
hertz
n/a
n/a
0.1
degrees
1
percent
1
percent
varies
milliseconds
n/a
n/a
Sync-Check (25) Protection
55
Default
Disabled
0
10
0.01
Disabled
0
0
0
50
0