Step 5:
Repeat step 4 for the 5,000 ms and 10,000 ms time delay settings of Table 158. Record the
results.
Step 6:
(Optional.) Repeat steps 1 through 5 for Settings group 1, 2, and 3.
Step 7:
(Optional.) Repeat steps 1 through 6 for 27X-2, 27X-3, and 27X-4.

Functional Test Report

Pickup Verification (3V0 Mode)
Pickup Setting Range = 1 to 150 V
Pickup Accuracy = ±2% or ±1 V, whichever is greater
Reset/Pickup Ratio = 102% ±1%
Step
Pickup Setting
6
115.0 V
7
65.0 V
7
20.0 V
* Reset range is calculated from the pickup setting and may need adjusted based on actual pickup.
Timing Verification (3V0 Mode)
Time Delay Range = 50 to 600,000 ms
Timing Accuracy = ±0.5% or ±2 cycles, whichever is greater
Step
Time Delay Setting
4
2,000 ms
5
5,000 ms
5
10,000 ms
Pickup Verification (V1 Mode)
Pickup Setting Range = 1 to 150 V
Pickup Accuracy = ±2% or ±1 V, whichever is greater
Reset/Pickup Ratio = 102% ±1%
Pickup
Setting
Step
V1
VA
V1
6
78.0
234.0
76.4
7
38.0
114.0
37.0
7
22.0
66.0
21.0
* Reset range is calculated from the pickup setting and may need adjusted based on actual pickup.
Auxiliary Undervoltage (27X) Test
Low
Actual Pickup
112.7 V
63.7 V
19.0 V
Low
1,968 ms
4,968 ms
9,950 ms
Low
Actual
Pickup
VA
V1
229.2
79.5
111.0
39.0
63.0
23.0
High
Low*
Actual Reset
117.3 V
116.2 V
66.3 V
65.7 V
21.0 V
20.2 V
Actual Timing
High
Low*
VA
V1
VA
238.5
78.7
236.1
117.0
38.3
114.9
69.0
22.2
66.6
9424200994 Rev U
Pass/Fail
High*
118.4 V
P / F
66.9 V
P / F
20.6 V
P / F
High
Pass/Fail
2,032 ms
P / F
5,032 ms
P / F
10,050 ms
P / F
High*
Actual
Pass/Fail
Reset
V1
VA
80.3
240.9
39.1
117.3
22.6
67.8
P / F
P / F
P / F
BE1-11g