Basler BE1-11g Instruction Manual page 129

Generator protection system
Hide thumbs Also See for BE1-11g:
Table of Contents

Advertisement

9424200994 Rev U
The impedance seen by the BE1-11g is calculated in Equation 18:
If V
and V
are very small (Equation 19):
0,Source
2,Source
Equation 19. Impedance with Small V
The calculations in the BE1-11g are account for the negative factor in the above equation and hence a
180° phase shift is implemented in the BE1-11g firmware so that a correct forward/reverse decision is
made.
The positive-sequence impedance as seen by the BE1-11g is quite a bit more complicated since V
is not negligible. One simple application to study is the three-phase fault and the B to C phase fault
(Equation 20):
Directional relaying would not be of much value in a radial system where all current flow will be forward. In
two source systems, as shown in Figure 71, a profile of sequence voltages in the system will show V
V
at either source. V
and V
2
0
conditions with their maximum value being at the fault location, with current flowing from X and Y in a
current division rule applied to the symmetrical component network that represents the fault impedances
and the fault type. Independent of the fault type and how the sequence currents divide in the system, the
sequence voltages and hence sequence impedances measured by the BE1-11g will still be dependent on
V
=V
- Z
I
Relay
Source
Source
Source
opposite direction as the direction to the fault, looking back toward the source. But for the three-phase
fault the BE1-11g will sense the positive-sequence impedance in the line between the BE1-11g and the
fault location. The sensed zero-sequence current can be shifted notably when zero-sequence coupling
between adjacent lines is involved. However, since a large phase angle window of ±90° from the MTA is
being utilized for directional decisions, the direction decision is not highly sensitive to zero-sequence
coupling effects.
BE1-11g
Equation 18. Impedance Seen by the BE1-11g
Equation 20. Three-Phase/B to C-Phase Faults
will still be negligible in normal operation, and show up only during fault
2
. The BE1-11g will sense the zero and negative-sequence impedances in the
and V
Source Voltages
0
2
Directional Overcurrent (67) Protection
117
1,Source
and
0