Functional Test Report

Pickup Verification (Phase Mode)
Pickup Setting Range = 0.5 to 16 A for 5A sensing
Pickup Accuracy =
Inverse Overcurrent (51) Test
Table 216. Timing Test Settings (IG Mode)
Sensing
Type
5 A
1 A
SEF
0.1 to 3.2 A for 1A sensing
±2% or ±50 mA, whichever is greater for 5A sensing
±2% or ±10 mA, whichever is greater for 1A sensing
Time
Applied
Dial
Current
1.00 A
0.5
2.50 A
12.50 A
1.00 A
5.0
2.50 A
12.50 A
1.00 A
9.9
2.50 A
12.50 A
0.20 A
0.5
0.50 A
2.50 A
0.20 A
5.0
0.50 A
2.50 A
0.20 A
9.9
0.50 A
2.50 A
0.20 A
0.5
0.50 A
0.80 A
0.20 A
5.0
0.50 A
0.80 A
0.20 A
9.9
0.50 A
0.80 A
9424200994 Rev U