Basler BE1-11g Instruction Manual page 266

Generator protection system
Hide thumbs Also See for BE1-11g:
Table of Contents

Advertisement

254
Setting
Block V2 Voltage Elements
Block Power/Power Factor
Elements
Block Impedance Elements
Ignore Breaker Status
Fuse Loss (60FL)
All functions that use the negative-sequence voltage (V2)
measurement are blocked when the 60FL logic is true. (27X, 59X -
V2 mode)
All functions that use the power measurements are blocked when
the 60FL logic is true. (32)
All functions that use the impedance measurement are blocked
when the 60FL logic is true. (21 and 40Z)
When enabled, breaker status is ignored.
9424200994 Rev U