9424200994 Rev U

Operational Settings

Loss of excitation - reverse var based element operational settings are configured on the Loss of
Excitation - Reverse var Based (40Q) settings screen (Figure 88) in BESTCOMSPlus. Setting ranges and
defaults are summarized in Table 51.
Figure 88. Loss of Excitation - Reverse var Based Settings Screen
Setting
Mode
0 or 1 to 6,000 (5A CTs) secondary
Pickup
0 or 1 to 1,200 (1A CTs) secondary
Time Delay
BE1-11g
Table 51. Operational Settings
Range
Disabled or Enabled
0 or 1 to 600,000
Loss of Excitation - Reverse Var Based (40Q) Protection
Increment
Unit of Measure
n/a
n/a
varies
vars
varies
milliseconds
141
Default
Disabled
0
0