Retrieving Alarm Information; Resetting Alarms - Basler BE1-11g Instruction Manual

Generator protection system
Hide thumbs Also See for BE1-11g:
Table of Contents

Advertisement

222
9424200994 Rev U
under Alarm Configuration. When active, the label of a user alarm is displayed on the Alarms screen on
the front-panel display and in the fault report and/or sequence of events report.
Figure 152. User Programmable Alarms Screen

Retrieving Alarm Information

BESTCOMSPlus Navigation Path: Metering Explorer, Status, Alarms
HMI Navigation Path: Metering Explorer, Status, Alarms
Major and Minor alarms can be viewed through BESTCOMSPlus, the front-panel display and LED
indicators, and the web page interface. Alarms are displayed in the fault reports and sequence of events
reports.
To view alarms at the front-panel display, navigate to Metering > Status > Alarms. All active alarms will be
shown on this screen. The front-panel navigation keys can be used to scroll through the list of active
alarms.
To view alarm status using BESTCOMSPlus, use the Metering Explorer to open the Status, Alarms
screen shown in Figure 153. Alarms can be reset by clicking the Reset Alarms button under the
appropriate column.
Figure 153. Alarms Screen

Resetting Alarms

A BESTlogicPlus expression can be used to reset the alarms. Use the Settings Explorer within
BESTCOMSPlus to open the BESTlogicPlus Programmable Logic tree branch. Select the Major Alarm
Reset, Minor Alarm Reset, or Logic Alarm Reset logic block from the list of Elements. The Major Alarm
Reset will reset all major alarms. The Minor Alarm Reset will reset all minor alarms. The Logic Alarm