Basler BE1-11g Instruction Manual page 157

Generator protection system
Hide thumbs Also See for BE1-11g:
Table of Contents

Advertisement

9424200994 Rev U
Setting
Select Delta/Wye
Compensation
Mode
Diameter
Time Delay
Torque Angle
Offset
BE1-11g
Figure 90. Distance Settings Screen
Table 53. Operational Settings
Range
None, DAB (+30), or DAC (–30)
Disabled or Enabled
0 to 500 secondary
0 to 300,000
0 to 90
–500 to 500 secondary
Unit of
Increment
Measure
n/a
n/a
n/a
n/a
varies
ohms
varies
milliseconds
1
degrees
varies
ohms
Distance (21) Protection
145
Default
Disabled
Disabled
0
0
45
0