Viewing The Security Log - Basler BE1-11g Instruction Manual

Generator protection system
Hide thumbs Also See for BE1-11g:
Table of Contents

Advertisement

346
Setting
Access Timeout Delay
Login Failure Login Attempts
Login Failure Login Time Window
Login Failure Lockout Time
HMI Login Required - Alarm Reset
HMI Login Required - Target Reset
1.
Use the Settings Explorer in BESTCOMSPlus to select Access Control under General Settings,
Device Security Setup. The Access Control screen is shown in Figure 267.
2.
Configure the Access Timeout and Login Failure settings.
3.
Pull down the Communication menu and select Upload Security to Device. The Login dialog box pops
up. An administrator level is required to upload security to the device.
4.
Enter the username and password of the administrator and then click the Log In button. The default
administrator username is "A" and the default password is "A". BESTCOMSPlus notifies you when
the upload is successful.

Viewing the Security Log

BESTCOMSPlus Navigation Path: Metering Explorer, Reports, Security Log
HMI Navigation Path: Not available through the front panel
The BE1-11g records information about user logins including the port used to log in, the access level
granted, the type of action performed, and the time of logout and creates security logs. A log will also be
triggered when a user attempts to log in, but fails due to an invalid username or incorrect password.
A maximum of 200 entries are stored in nonvolatile memory. When a new entry is generated, the
BE1-11g discards the oldest of the 200 entries and replaces it with a new one.
Use the Metering Explorer to open the Reports, Security Log screen. If an active connection to a BE1-11g
is present, the security log will automatically download. Using the Options button, you can copy, print, or
save the security log. The Refresh button is used to refresh/update the security log. The Clear button
clears the security log. The Toggle Sorting button enables sorting. Click on a column header to sort. See
Figure 268.
Security
Table 113. Settings for Access Control
Range
10 to 3,600
1 to 10
1 to 99,999
1 to 99,999
Enabled or Disabled
Enabled or Disabled
Figure 268. Security Log
9424200994 Rev U
Increment
Unit
1
seconds
1
units
1
seconds
1
seconds
n/a
n/a
n/a
n/a
Default
300
1
1
1
Enabled
Enabled
BE1-11g