14920
[Channel %1: ] Block %2 intermediate point of circle incorrect
Parameters:
%1 = Channel number
%2 = Block number, label
Explanation:
When programming a circle by means of an intermediate point (CIP) all 3 points (initial, end and intermediate points) are
on a straight line and the intermediate point (programmed by means of interpolation parameters I, J, K) is not located
between the initial and end points.
If the circle is the component of a helix, the specified number of turns (keyword TURN=...) determines further block
processing:
- TURN>0: alarm display because the circle radius is infinitely great.
- TURN=0 and CIP specified between initial and end points. A straight line is generated between the initial and end points
(without alarm message).
Reaction:
Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy:
Locate the position of the intermediate point with the parameters I, J and K in such a way that it actually is located between
the initial and end points of the circle or do not make use of this type of circle programming and instead program the circle
with radius or opening angle or center point parameters.
Programm
Clear alarm with NC START or RESET key and continue the program.
continuation:
15030
[Channel %1: ] Block %2 different measurement system settings
Parameters:
%1 = Channel number
%2 = Block number, label
Explanation:
The INCH or METRIC instruction describes the system of measurement in which the data blocks have been read from the
control. In order to prevent the incorrect interpretation of data intended for a particular system of measurement, a data
block is only accepted if the above instruction matches the active system of measurement.
Reaction:
Interpreter stop
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy:
Change the system of measurement or load a data block which matches the system of measurement.
Programm
Clear alarm with the RESET key. Restart part program
continuation:
15100
[Channel %1: ] Block %2 REORG cancelation caused by log file overflow
Parameters:
%1 = Channel number
%2 = Block number, label
Explanation:
In order to synchronize the preprocessing run and the main run with REORG, the control accesses modification data which
are maintained in a logfile. The alarm indicates that no more capacity is available in the logfile for the specified block in
the channel.
Reaction:
Interpreter stop
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy:
Please inform the authorized personnel/service department. No remedial measures are available for the further execution
of the current part program, however:
1. Reduce log file size requirement by:
Reducing the distance between the preprocessing and the main run via appropriate preprocessing stops STOPRE.
2. Increase the size of the logfile by means of the channel-specific machine data:
MD28000 $MC_MM_REORG_LOG_FILE_MEM and
MD 28010 $MC_MM_NUM_REORG_LUD_MODULES
Programm
Clear alarm with the RESET key. Restart part program
continuation:
Diagnostics Manual
Diagnostics Manual, 06/2015, 6FC5398-6DP10-0BA2
SINUMERIK 808D ADVANCED alarms
5.2 NCK alarms
227