Explanation:
The machine kinematics does not allow the specified motion. Transformation-dependent error causes can be in:
TRANSMIT: A (circular) area exists around the pole, where positioning is not possible. The area is caused by the fact that
the tool reference point cannot be traversed as far as into the pole.
The area is defined by:
- the machine data (MD24920 $MC_TRANSMIT_BASE_TOOL..)
- the active tool length compensation (see $TC_DP..). Whether the tool length compensation is included in the calculation
depends on the working plane selected (see G17,..).
- The machine stops before the faulty block.
Reaction:
Interpreter stop
Local alarm reaction.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy:
Modify part program. Change the incorrectly specified tool length compensation.
Programm
Clear alarm with the RESET key. Restart part program
continuation:
10915
[Channel %1: ] Block %2 Preparation problem in LookAhead (Identifier %3, Details %4)
Parameters:
%1 = Channel number
%2 = Block number, label
%3 = Error code
%4 = Error details
Explanation:
The NCK was incorrectly parameterized (under certain circumstances, the parameterized memory is not sufficient), which
is why LookAhead can no longer be operated in the expansion mode.
Reaction:
Interpreter stop
Local alarm reaction.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy:
Change parameterization (increase LookAhead memory and/or IPO buffer, change tolerances). Use standard LookAhead.
Contact Siemens if necessary.
Programm
Clear alarm with the RESET key. Restart part program
continuation:
10916
[Channel %1: ] Block %2 Preparation problem in LookAhead (Identifier %3, Details %4)
Parameters:
%1 = Channel number
%2 = Block number, label
%3 = Error code
%4 = Error details
Explanation:
The NCK was incorrectly parameterized (under certain circumstances the parameterized memory is not sufficient), this is
the reason that the generated profile is not as smooth and uniform as it could be.
Reaction:
Local alarm reaction.
Alarm display.
Warning display.
Remedy:
Change the parameterization (increase the LookAhead memory and/or IPO buffer, change tolerances).
1010: Increase IPO buffer to at least 50 blocks, or maximum number of blocks in the braking ramp times 2.
Programm
Clear alarm with the Delete key or NC START.
continuation: