Arrangement of the Measuring Input Terminals
IM 04P01B01-01E
• To minimize noise caused by electromagnetic induction, twist the measurement circuit
wires at short, equal intervals.
• Make sure to earth ground the protective ground terminal through minimum
resistance.
When using internal reference junction compensation on the thermocouple
input, take measures to stabilize the temperature at the input terminal.
• Always use the terminal cover.
• Do not use thick wires which may cause large heat dissipation (cross sectional area of
2
0.5 mm
or less recommended).
• Make sure that the ambient temperature remains reasonably stable. Large
temperature fluctuations can occur if a nearby fan turns ON or OFF.
Connecting the input wires in parallel with other devices can cause signal
degradation, affecting all connected devices.
If you need to make a parallel connection, then
• Turn the burnout detection function OFF.
• Ground the instruments to the same point.
• Do not turn ON or OFF another instrument during operation. This can have adverse
effects on the other instruments.
• RTDs cannot be wired in parallel.
A terminal cover is screwed in place on the measuring input terminal block on the rear
panel. A label indicating the terminal arrangement is affixed to the cover.
Terminal cover
attachment screws
Pen Model
b
+/A
Channel 1
Channel 2
Channel 3
Channel 4
Screw input terminal
Measuring input terminal block
+/A
Channel 2
b
Channel 4
Clamped input terminal
(/H2 option)
2.3 Input Signal Wiring
+/A
Channel 1
b
Channel 3
2-5
1
2
3
4
5
6
7
8
9
10
11
12
App
Index

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents