6.13 Performing Calibration Correction (/CC1
Option)
Procedure
6-14
The values of the measuring input signal are corrected using specified segments, and
the results are used as measured values.
If you change the input range, set the correction point (measured value) and correction
values again.
1.
Hold down the
MENU
2.
key or SHIFT +
Press the
key.
3.
Set each item and press the
Use the
key or SHIFT +
For the procedure on how to enter values or characters, see section 4.2.
If you press the ESC key in the middle of the operation, the settings entered up to
then are cancelled, and the display returns to a higher level menu.
4.
When the Setting complete screen appears, do either of the following:
Press the
key to set other channels.
If you are done, press the ESC key.
5.
Hold down the
MENU
Set=Calibration
CH=01
(Displays the following when
Calibration is On)
Calibration=On
1 datums=
1 revise=
Decision=Yes
01CH Calibration
ESC/?
Setting complete
key for 3 seconds to enter Setting mode.
key to select Calibration and then press the
key.
key to select values.
key for 3 seconds to return to Operation mode.
Select the channel.
Turn On or Off the calibration correction.
Set the first correction point
0.000
(input value).
Set the first correction value.
0.000
Likewise, set the second correction
.
.
point and correction value.
.
Yes: The setting is fixed.
No: The setting becomes invalid.
The new setting takes effect.