YOKOGAWA MuR10000 Manual page 117

Table of Contents

Advertisement

IM 04P01B01-01E
Alarm Value
• High Limit Alarm/Low Limit Alarm and Delay High Limit Alarm/Delay
Low Limit Alarm
The following values can be specified.
• For DC voltage, TC, and RTD input: Values within the measurable range in the
specified range (example: –2.000 to 2.000 V for the 2 V range).
• For ON/OFF input (DI): 0 or 1.
• For linear scaling (1-5V, scaling, and square root): A value within –5 to 105% of
the scaling span (version 1.11 or later) except within the range of –20000 to 30000
(excluding the decimal point).
Note
For channels whose the leftmost value of the scale is set to –20000 (excluding the decimal),
the alarm value of –20000 is invalid. Set a value that is greater than or equal –19999.
• Difference High Limit Alarm/Difference Low Limit Alarm
Values in the measurable range can be specified. Measurable range refers to
"Selectable Span Range" in the table on page 5-4.
• High Limit on Rate-of-Change Alarm/Low Limit on Rate-of-Change Alarm
A value greater than or equal to 1 digit can be specified. For example, 1 digit
corresponds 0.001 for the 2 V range (measurable range: –2.000 to 2.000 V). The
maximum value that can be specified is the width of the measurable range (4.000 V
for 2 V range).
For ON/OFF input, only "1" can be specified.
Relay No.
The selectable relay numbers are listed below.
I01 and I02 on the /A1 option
I01, I02, I03, and I04 on the /A2 option
I01, I02, I03, I04, I05, and I06 on the /A3 option
5.2 Setting the Alarm
Index
5-11
1
2
3
4
5
6
7
8
9
10
11
12
App

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents