6.1 Setting the Trend Recording Interval (Dot Model)
6-2
Example of calculating the dot printing interval when the trend recording
interval is set to auto
μR10000 6-dot model
A/D integrate: Auto
Chart speed: 23 mm/h
Number of recording channels: 6 channels
Scan interval = 1 s
A value that is less than or equal to 900 ÷ chart speed and that is the largest integer
multiple of the scan interval = 39 s
Because this 39 s is within the range of the fastest (= 10 s) to 90 s, recording interval =
39.0 s