Chapter 5
Frequently Used Setup Operations (Setting Mode)
5.1

Setting the Input Range

Procedure
TC, RTD, and DC Voltage
IM 04P01B01-01E
Input range is set for each measurement channel. Set unused channels to Skip.
• The input range cannot be changed on models with the computation function (/M1
option) when computation is in progress.
• If you change the input range, set the bias, alarm, partial expanded recording, and
calibration correction again.
1.
Hold down the
key for 3 seconds to enter Setting mode.
MENU
2.
Press the
key with Range shown on the screen.
3.
Set each item and press the
Use the
key or SHIFT +
For the procedure on how to enter values or characters, see section 4.2.
If you press the ESC key in the middle of the operation, the settings entered up to
then are cancelled, and the display returns to a higher level menu.
4.
When the Setting complete screen appears, do either of the following:
Press the
key to set other channels.
If you are done, press the ESC key.
5.
Hold down the
key for 3 seconds to return to Operation mode.
MENU
Set=Range
CH=01-01
First channel
Last channel
Mode=TC
Range=R
Span_L=
Span_R= 1760.0
01-01 Channel
ESC/?
Setting complete
key.
key to select values.
Set the channel range.
Select TC, RTD, or Volt.
Select the range type.
Select the left span value.
0.0
Select the right span value.
The new setting takes effect.
1
2
3
4
5
6
7
8
9
10
11
12
App
Index
5-1