Alarm Indication

Alarm Recording
Alarm Output Relay (/A1, /A2, and /A3 Options)
IM 04P01B01-01E
The alarm status can be displayed on the screen. For details on the display, see section
1.5.
Non-Hold/Hold Operation of the Alarm Indication
The alarm indication can be set to operate in the following fashion when the alarm
condition is no longer met.
• Clear the alarm indication (non-hold).
• Hold the alarm indication until the alarm ACK operation is executed (hold).
The default setting is non-hold.
Non-hold
Alarm occurrence
Alarm
Alarm release
ON
Alarm
indication
OFF
<Related Topics> Setting the non-hold/hold operation of the alarm indicator: Section 7.1
The alarm occurrence/release can be recorded on the chart paper. See section 1.4.
Contact signals can be generated from alarm output relays when alarms occur. The
number of output relays is 2 (/A1), 4 (/A2), or 6 (/A3). The alarm output relays are
denoted as I01 to I06 on the recorder.
The following functions can be assigned to the alarm output relay.
Diagnosis Output
The diagnosis output can be assigned to alarm output relay I01.
The relay is activated when there is an error in the plotter operation on the pen model,
when a burnout is detected, or when there is an error in the A/D converter. Output relay
I01 is normally energized and de-energizes when an error is detected (de-energized
operation and non-hold operation).
NO
C
NC
NO
Normal
Malfunction
NO: Normally Opened, C: Common, NC: Normally Closed
Note
If diagnosis output is enabled, I01 becomes a relay dedicated to diagnosis output.
<Related Topics> Setting the diagnosis output: Section 7.1
For the procedure to set the functions, see section 1.10, "Function Setup Guide."
Hold
Alarm ACK
or
Blinking
or
OFF
C
NC
NO
C
NC
Power-OFF
1.3 Alarms
Alarm ACK
Blinking
ON
OFF
1-9