5.1 Setting the Input Range
1-5V Input
5-6
Set=Range
CH=01-01
First channel
Last channel
Mode=1-5V
Span_L=
Span_R=
Scale_L=
Scale_R= 200.00
(When low-cut is set to Use)
Low-cut=Off
01-01 Channel
ESC/?
Setting complete
Description
• Span Left and Span Right
Selectable span left range: 0.8 to 1.2 V
Selectable span right range: 4.8 to 5.2 V
• Scale Left, Scale Right, and Decimal Place
Selectable range (mantissa): –20000 to 30000
Example: T he value in the range of –100.00 to 350.00 cannot be specified. The
mantissa of Scale_R is 35000, which exceeds the upper limit of 30000. Set
in the range of –100.0 to 350.0.
Decimal place: XXXXX, XXXX.X, XXX.XX, XX.XXX, X.XXXX
The decimal place is set using Scale_L. It cannot be set using Scale_R.
Example: Change 0.00 to 0.0.
Press the
Press the
Make sure that scale left is less than scale right.
• Low-cut
On: Cuts values below 0% of the recording span (set to 0% (scale left value)).
Off: Does not apply the low-cut function.
<Related Topics> Setting the unit: Section 5.3
Enab ling the low-cut function: Section 7.15
Set the channel range.
Select 1-5V.
Set the left span value.
1,000
Set the right span value.
5,000
Set the decimal place
0.00
and left scale value.
Set the right scale value.
Turn On or Off the low-cut function.
The new setting takes effect.
key to move the cursor to the last digit of 0.00.
key to change the value to 0.0 .
Space
IM 04P01B01-01E

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents