Digital Inputs - Siemens SINAMICS G120 Operating Instructions Manual

Frequency converter
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Adapting the terminal strip

7.1 Digital inputs

7.1
Digital inputs
Digital input terminals
Table 7- 1
BI
p0810 Command data set selection CDS bit 0
p0840 ON/OFF1
p0844 OFF2
p0848 OFF3
p0852 Enable operation
p0855 Unconditionally release holding brake
p0856 Enable speed controller
p0858 Unconditionally close holding brake
p1020 Fixed speed setpoint selection bit 0
p1021 Fixed speed setpoint selection bit 1
p1022 Fixed speed setpoint selection bit 2
p1023 Fixed speed setpoint selection bit 3
p1035 Motorized potentiometer, setpoint, raise
A complete list of the binector outputs is provided in the List Manual.
Table 7- 2
Acknowledge fault with digital input 1:
Switch-on motor with digital input 2:
74
BI: pxxxx
r0722.0
r0722.1
r0722.2
r0722.3
r0722.4
r0722.5
Binector inputs (BI) of the converter (selection)
Significance
Examples:
p2103
r0722.1
722.1
p0840
r0722.2
722.2
Changing the function of the digital input
Interconnect the status parameter of the digital input with a
binector input of your choice.
Binector inputs are marked with "BI" in the parameter list of the List
Manual.
BI
p1036 Motorized potentiometer, setpoint, lower
p1055 Jog bit 0
p1056 Jog bit 1
p1113 Setpoint inversion
p1201 Flying restart enable signal source
p2103 1. Acknowledge faults
p2106 External fault 1
p2112 External alarm 1
p2200 Technology controller enable
p3330 Two-wire/three-wire control, control
p3331 Two-wire/three-wire control, control
p3332 Two-wire/three-wire control, control
With Operator Panel
Set p2103 = 722.1
Set p0840 = 722.2
Operating Instructions, 03/2012, FW V4.5, A5E02999804B AB
Significance
command 1
command 2
command 3
In STARTER
Go online with STARTER
and select "inputs/outputs".
Change the input function
via the corresponding
screen form.
SINAMICS G120C frequency converter

Advertisement

Table of Contents
loading

Table of Contents