QFX10000 Clearance Requirements for Airflow and Hardware Maintenance
Copyright © 2019, Juniper Networks, Inc.
Installing the QFX10008 into a Rack on page 152
Mounting a QFX10016 in a Four-Post Rack Using a Mechanical Lift
When planning the site for a QFX10008 or QFX10016 installation, you must allow sufficient
clearance around the installed chassis for cooling and maintenance (see
Figure 57 on page 121
for QFX10008 and
Figure 57: Clearance Requirements for Airflow and Hardware Maintenance for a
QFX10008 Modular Chassis
Figure 58: Clearance Requirements for Airflow and Hardware Maintenance for a QFX10016
Modular Chassis
24" ( 6 1cm)
Front mounting flange
Clearan ce requi red
for main t enan ce
Ports
19"
(4 8 .3 cm)
(Mounting
flange
width)
5.1" (13 cm.)
Cable management depth
6.1" (15.5 cm.)
Front panel depth
12" (30.5 cm.)
For airflow
Chapter 2: Site Planning, Preparation, and Specifications
Figure 58 on page 121
for QFX100016).
Clearan ce requi red
f or main t enan ce
35 "
(88 .9 cm)
3" (7.6 cm)
32 "
(81 .3 cm)
12" (30.5 cm)
For airflow
24 " ( 6 1cm)
FRUs
17.4"
(4 4 .2 cm)
4 " (10.2 cm)
Power cable depth
121