Figure 108: Installing an AC Power Supply in a QFX10016

Attach each power cord to a dedicated AC power source outlet.
11.
Squeeze the two sides of the power cord retainer clip and insert the ends of the clip
12.
into the holes in the bracket on each side of the AC appliance inlets on the AC power
supply faceplate. See
Figure 109 on page
Locate two power cords shipped with the switch; the cords have plugs appropriate
13.
for your geographical location.
Insert the power cord coupler into the power supply.
14.
Each AC power supply has two independent 16 A rated AC inlets on the faceplate.
Each inlet must be connected to a dedicated AC power feed to achieve 2N source
redundancy. If redundancy is not a requirement, use the default input
connection.
Fasten the cord retainer by lowering the clip over the cord and pushing the cord into
15.
the adjustment nut of the cord retainer. Rotate the nut until it is tight against the base
of the cord. See
Figure 109 on page
Keep latch in open position during installation.