Figure 116: Removing The Plastic Cable Cover On A Qfx10000 Dc Power - Juniper QFX10008 Hardware Manual

Hide thumbs Also See for QFX10008:
Table of Contents

Advertisement

Copyright © 2019, Juniper Networks, Inc.
Remove the plastic cable cover from the DC power input terminals by using the
5.
Phillips (+) screwdriver, number 2, to loosen the screws (see
Figure 116: Removing the Plastic Cable Cover on a QFX10000 DC Power Supply
Remove the nuts from each DC power input terminal, using the 13/32 in. (10 mm) nut
6.
driver or socket wrench to loosen the nuts.
Ensure that the power source circuit breaker is open so that the voltage across the
7.
DC power source cable leads is 0 V and that the cable leads do not become active
while you are connecting DC power.
Install a power lug on each DC power cable. Ensure the lug meets the double hole
8.
standard lug terminal for 4 AWG wire. The lugs should be dual, 1/4 in. spaced 5/8 in.
apart. The terminal must accommodate double hole standard lug terminal for 4 AWG
or larger wire.
Verify that the DC power cables are correctly labeled before making connections to
9.
the power supply. In a typical power distribution scheme where the return is connected
to chassis ground at the battery plant, you can use a multimeter to verify the resistance
of the
–48V
and
RTN
DC cables to chassis ground:
Chapter 4: Maintaining Components
Figure 116 on page
203).
203