Table 54: Line Card Power Consumption (continued)
Number
of Line
Cards
QFX10000-36Q
7
4725 W
8
5400 W
Copyright © 2019, Juniper Networks, Inc.
QFX10000-30C
QFX10000-30C-M
8050 W
8750 W
9200 W
10000 W
NOTE:
The QFX10000-12C-DWDM line card is designed to comply with
NEBS regulations on the QFX10000 line of modular switch chassis when
these switches are used in typical configurations. In a typical configuration,
a QFX10008 switch supports up to eight line cards, with up to four
QFX10000-12C-DWDM in any of the eight slots.
To comply with EMC regulations, you must also install front panel on the
QFX10008 chassis. See
For example, for a QFX10008 with five QFX10000-36Q line cards and three
QFX10000-30C, the maximum power consumption is:
= 5 (power consumed by QFX10000-36Q in watts) + 3 (power consumed by
QFX10000-30C line cards in watts)
= 5 (675 W) + 3 (1150 W)
= (3375 W + 3450 W)
= 6825 W
Add the power consumption from step
3.
step 2.
To continue from the previous example, add the wattage from five QFX10000-36Q
and three QFX10000-30C cards to a redundant configuration.
(6825 W) + (2560 W)
= 9385 W required
Calculating the Number of Power Supplies Required for Your QFX10008

Configuration

Use this procedure to calculate the number of power supplies required by your switch
configuration. The minimum power configuration for QFX10008 switches is three power
supplies.
Chapter 2: Site Planning, Preparation, and Specifications
QFX10000-60S-6Q
3185 W
3640 W
"QFX10000 EMI Front Panel" on page
1
and the total line card consumption from
QFX10000-12C-DWDM
39.