SRX1400 Services Gateway Grounding Cable Specification

Related
Documentation

SRX1400 Services Gateway DC Power Specifications and Requirements

SRX1400 Services Gateway DC Power System Electrical Specifications

Related
Documentation
Copyright © 2011, Juniper Networks, Inc.
Appendix B: SRX1400 Services Gateway Power Guidelines, Requirements, and Specifications
The grounding cable that you provide must be 6-AWG (13.3 mm
or as permitted by the local code.
WARNING: The services gateway is pluggable type A equipment installed in
a restricted-access location. It has a separate protective earthing terminal
(sized for M5 screws) provided on the chassis in addition to the grounding
pin of the power supply cord. This separate protective earthing terminal must
be permanently connected to earth.
SRX1400 Services Gateway Chassis Grounding Point on page 181
SRX1400 Services Gateway Grounding-Cable Lug Specification on page 182
Grounding the SRX1400 Services Gateway on page 78
SRX1400 Services Gateway Front Panel on page 14
This topic includes the following sections:
SRX1400 Services Gateway DC Power System Electrical Specifications on page 183
SRX1400 Services Gateway DC Power Supply Electrical Specifications on page 184
Power Requirements for DC-Powered SRX1400 Services Gateways on page 185
SRX1400 Services Gateway DC Power Cable Specifications on page 186
Table 39 on page 183 lists the DC power system electrical specifications.
Table 39: DC Power System Electrical Specifications
Item
DC input voltage
DC system current rating
Maximum DC input power
SRX1400 Services Gateway DC Power Supply Electrical Specifications on page 184
Power Requirements for DC-Powered SRX1400 Services Gateways on page 185
SRX1400 Services Gateway DC Power Cable Specifications on page 186
SRX1400 Services Gateway DC Power Supply on page 35
Specification
Operating range: – 40 to – 72 VDC
10.1 A @ - 48 VDC
485 W
2
), minimum 60°C wire,
183