END USER LICENSE AGREEMENT The Juniper Networks product that is the subject of this technical documentation consists of (or is intended for use with) Juniper Networks software. Use of such software is subject to the terms and conditions of the End User License Agreement (“EULA”) posted at http://www.juniper.net/support/eula.html.
Page 4
Cooling System Description ........47 SRX1400 Services Gateway Cooling System ......47 Chapter 6 Power System Description .
Page 5
Required Tools and Parts for Unpacking the SRX1400 Services Gateway ..93 Unpacking the SRX1400 Services Gateway ......93 Verifying Parts Received with the SRX1400 Services Gateway .
Page 6
SRX1400 Services Gateway Chassis Grounding Point ..... . 121 Grounding the SRX1400 Services Gateway ......123 Chapter 21 Connecting the SRX1400 Services Gateway to External Devices .
Page 7
Replacing a Network Processing Card on the SRX1400 Services Gateway ..187 Replacing an SPC on the SRX1400 Services Gateway ..... 189 Chapter 29 Replacing Cooling System Components .
Page 8
Contacting Customer Support ........209 Return Procedure for the SRX1400 Services Gateway ..... 210 Listing the SRX1400 Services Gateway Component Serial Numbers with the CLI .
Page 9
Agency Approvals and Regulatory Compliance Information ... 267 SRX1400 Services Gateway Agency Approvals ......267 SRX1400 Services Gateway Compliance Statements for EMC Requirements .
Page 11
System Overview ........... 3 Figure 1: SRX1400 Services Gateway Data Flow ......7 Chapter 2 Hardware Component Overview .
Page 12
Cooling System Description ........47 Figure 30: SRX1400 Services Gateway Fan Tray ......47 Chapter 6 Power System Description .
Page 13
Chapter 20 Grounding the SRX1400 Services Gateway ......121 Figure 52: Grounding Point on the SRX1400 Services Gateway ....122 Figure 53: Connect the Grounding Cable to the SRX1400 Services Gateway .
Page 14
Figure 81: Typical DC Source Cabling to the SRX1400 Services Gateway ..203 Figure 82: SRX1400 Power Supply Air Filter ......206 Chapter 31 Contacting Customer Support .
® To obtain the most current version of all Juniper Networks technical documentation, see the product documentation page on the Juniper Networks website at http://www.juniper.net/techpubs/ If the information in the latest release notes differs from the information in the documentation, follow the product Release Notes.
SRX1400 Services Gateway Hardware Guide Table 1: Notice Icons Icon Meaning Description Informational note Indicates important features or instructions. Caution Indicates a situation that might result in loss of data or hardware damage. Warning Alerts you to the risk of personal injury or death.
We encourage you to provide feedback, comments, and suggestions so that we can improve the documentation. You can provide feedback by using either of the following methods: Online feedback rating system—On any page of the Juniper Networks TechLibrary site , simply click the stars to rate the content, http://www.juniper.net/techpubs/index.html and use the pop-up form to provide us with information about your experience.
7 days a week, 365 days a year. Self-Help Online Tools and Resources For quick and easy problem resolution, Juniper Networks has designed an online self-service portal called the Customer Support Center (CSC) that provides you with the following features: Find CSC offerings: http://www.juniper.net/customers/support/...
The SRX1400 Services Gateway is three rack units (U) tall. Sixteen devices can be stacked in a single floor-to-ceiling rack, for increased port density per unit of floor space. The device provides three common form-factor module (CFM) slots that can be populated with various CFM cards.
6 Understanding the SRX1400 Services Gateway in the Data Center on page 6 SRX1400 Services Gateway Models The SRX1400 Services Gateway is available in four models, which are listed in Table 3 on page Table 3: SRX1400 Services Gateway Models...
The SRX1400 Services Gateway accomplishes these tasks using the following features: A stateful firewall, including denial of service/distributed denial of service (DoS/DDoS) protection...
Understanding the SRX1400 Services Gateway in the Service Provider Network on page 6 Understanding the SRX1400 Services Gateway in the Data Center on page 6 Understanding the SRX1400 Services Gateway in the Service Provider Network The services gateway can be used in the service provider network to provide secure hosting and network services.
SRX1400 Services Gateway Models on page 4 Documentation SRX1400 Services Gateway Hardware Features on page 4 Understanding the SRX1400 Services Gateway in the Enterprise Network on page 5 Understanding the SRX1400 Services Gateway in the Service Provider Network on page 6...
Understanding the SRX1400 Services Gateway Data Flow on page 7 SRX1400 Services Gateway Backplane The backplane in the SRX1400 Services Gateway is in the rear of the chassis and provides connections for all cards and power supplies through the front of the chassis.
Overview of the SRX1400 Services Gateway CFMs on page 10 SRX1400 Services Gateway SYSIOCs The System I/O card (SYSIOC)s supported on the SRX1400 Services Gateway provide fixed I/O ports for the base system and are an important element of the data plane.
Chapter 2: Hardware Component Overview Figure 4: SRX1400 Services Gateway 10-Gigabit Ethernet SYSIOC This topic provides the following information about SRX1400 Services Gateway System I/O Cards: Features and Functions on page 13 POWER Button Functionality on the System I/O Card on page 13...
LED Indicators on the System I/O Card Figure 5 on page 14 shows the SRX1400 Services Gateway SYSIOC LEDs. Figure 5: SRX1400 Services Gateway SYSIOC LEDs Table 9 on page 14 describes the system behavior indicated by the various LEDs on the front panel of the SYSIOC.
Page 40
SRX1400 Services Gateway Hardware Guide Table 9: System I/O Card LED Indicators (continued) Label Color Status Indicated Behavior Green On steadily Chassis clustering is operating normally. All cluster members and all chassis cluster links are available. Amber On steadily An alarm is present on the chassis cluster link. All cluster members are present, but some chassis cluster links are down.
LED becomes solid green. NOTE: The LED labeled is currently not supported in this release. Table 10 on page 17 describes the Ethernet port LEDs. Table 10: SRX1400 Services Gateway Ethernet Port LEDs Color State Description Green On steadily Link is active.
Documentation SRX1400 Services Gateway Hardware Components on page 9 Troubleshooting the System I/O Card on the SRX1400 Services Gateway on page 162 Replacing the SYSIOC on the SRX1400 Services Gateway on page 185 IOCs and NP-IOCs Supported on the SRX1400 Services Gateway I/O cards (IOCs) are common form-factor module (CFM) cards that provide additional physical network connections to the services gateway.
Contact your Juniper Networks customer service representative for more information. Related Installing an IOC or NP-IOC in an SRX1400 Services Gateway on page 115 Documentation SRX1400 Services Gateway Routing Engine The Routing Engine is a PowerPC platform that runs Junos operating system (Junos OS).
Overview of the SRX1400 Services Gateway CFMs on page 10 Documentation SRX1400 Services Gateway Hardware Components on page 9 Maintaining the Routing Engine on the SRX1400 Services Gateway on page 151 Replacing a Routing Engine on the SRX1400 Services Gateway on page 177 SRX1400 Services Gateway NSPC...
1 and 3 in order to operate. You can install an NSPC, which contains an NPU and an SPU, or you can install a combination of SRX3000 Series Services Gateway NPC and SPC, on the SRX1400 Services Gateway. You must use a double-wide tray with the combination of NPC and SPC.
IKE negotiation. There are two places where you can install an SPC in your SRX1400 Services Gateway: You can install an SPC in the front-panel slot labeled if you also install an NPC in the slot labeled .
SRX1400 Services Gateway. Figure 13: SRX1400 Services Gateway Front Panel Table 13 on page 25 lists the components on the front panel of the services gateway. Table 13: SRX1400 Services Gateway Components on the Front Panel Number Component NSPC in CFM slots...
This guide shows the names for all of the front panel slots. Figure 15: SRX1400 Services Gateway Front Panel Slot Label Guide Table 15 on page 27 describes the different slots and their functions.
Routing Engines SRX3K-RE-12-10 and SRX1K-RE-12-10 on page 43 SRX1400, SRX3400, and SRX3600 Services Gateway Module Overview The modules described in this guide let you upgrade and customize your SRX1400, SRX3400, or SRX3600 Services Gateway to suit the needs of your network. The following...
Related Modules Supported on SRX1400, SRX3400, and SRX3600 Services Gateways on Documentation page 30 Eligible Slots for SRX1400, SRX3400, and SRX3600 Services Gateway Modules on page 31 Installing Common Form Factor Modules In SRX1400, SRX3400, and SRX3600 Services Gateways Modules Supported on SRX1400, SRX3400, and SRX3600 Services Gateways...
Table 17 on page 31 summarizes the slots in which you can install each module type for SRX1400, SRX3400, and SRX3600 Services Gateways. Table 17: Supported Slots for SRX1400, SRX3400, and SRX3600 Services Gateway Modules Supported Slots Module Name and Number...
Page 56
SRX1400 Services Gateway Hardware Guide Table 17: Supported Slots for SRX1400, SRX3400, and SRX3600 Services Gateway Modules (continued) Supported Slots Module Name and Number SRX1400 SRX3400 SRX3600 “Network Processing Card Slot (When installed as the Rear slots labeled Rear slots labeled SRX3K-NPC”...
Chapter 4: Line Card and Module Description Modules Supported on SRX1400, SRX3400, and SRX3600 Services Gateways on page 30 Installing Common Form Factor Modules In SRX1400, SRX3400, and SRX3600 Services Gateways Services Processing Card SRX3K-SPC-1-10-40 The SRX3K-SPC-1-10-40 Services Processing Card (SPC)
SR X3K -SP C-1 -10 -40 Related SRX1400, SRX3400, and SRX3600 Services Gateway Module Overview on page 29 Documentation Modules Supported on SRX1400, SRX3400, and SRX3600 Services Gateways on page 30 Eligible Slots for SRX1400, SRX3400, and SRX3600 Services Gateway Modules on...
Chapter 4: Line Card and Module Description Figure 18: Network Processing Card SRX3K-NPC SR X3K -NP Description NPC for SRX3400, SRX3600, and SRX1400 Power requirement: 64 W maximum Weight: 2.2 lb (1.0 kg) Software release Junos OS Release 9.3 and later...
Serial number label SR X3K -NP Related SRX1400, SRX3400, and SRX3600 Services Gateway Module Overview on page 29 Documentation Modules Supported on SRX1400, SRX3400, and SRX3600 Services Gateways on page 30 Eligible Slots for SRX1400, SRX3400, and SRX3600 Services Gateway Modules on...
SRX1400 Services Gateway Hardware Guide Eligible Slots for SRX1400, SRX3400, and SRX3600 Services Gateway Modules on page 31 Installing Common Form Factor Modules In SRX1400, SRX3400, and SRX3600 Services Gateways I/O Card SRX3K-16GE-SFP The SRX3K-16GE-SFP IOC (Figure 22 on page 38) adds 16 ports for Gigabit Ethernet traffic from either copper or fiber interface media.
SRX1400 Services Gateway Hardware Guide Installing Common Form Factor Modules In SRX1400, SRX3400, and SRX3600 Services Gateways I/O Card SRX3K-2XGE-XFP The SRX3K-2XGE-XFP (Figure 24 on page 40) IOC adds two ports for 10-Gigabit Ethernet traffic from fiber interface media. It is inserted horizontally into the midplane of the services gateway to communicate with the Switch Fabric Board (SFB) and to receive power.
IOCs Similar) Serial number label Related SRX1400, SRX3400, and SRX3600 Services Gateway Module Overview on page 29 Documentation Modules Supported on SRX1400, SRX3400, and SRX3600 Services Gateways on page 30 Eligible Slots for SRX1400, SRX3400, and SRX3600 Services Gateway Modules on...
For detailed information about supported transceivers, see the SRX Series Services Gateway Transceiver Guide www.juniper.net/techpubs/ Description 2-port Ethernet SFP+ NP-IOC for SRX3400, SRX3600, and SRX1400 Services Gateways Power requirement: 52 W maximum Weight: 2.4 lb (1.1 kg) Maximum configurable MTU: 9192 bytes Software release Junos OS Release 12.1X44-D10 and later...
IOCs Similar) Serial number label Related SRX1400, SRX3400, and SRX3600 Services Gateway Module Overview on page 29 Documentation Modules Supported on SRX1400, SRX3400, and SRX3600 Services Gateways on page 30 Eligible Slots for SRX1400, SRX3400, and SRX3600 Services Gateway Modules on...
Routing Engine in slot RE0. Figure 28: Routing Engine (SRX3K-RE-12-10 Shown, SRX1K-RE-12-10 Similar) Description Routing Engine for SRX1400 Services Gateway (SRX1K-RE-12-10) Routing Engine for SRX3400 or SRX3600 Services Gateway (SRX3K-RE-12-10) Power requirement: 53 W maximum Weight: 2.9 lb (1.3 kg) Software release SRX3K-RE-12-10: Junos OS Release 9.3 and later...
Figure 29: Routing Engine Serial Number Label Serial number label Related SRX1400, SRX3400, and SRX3600 Services Gateway Module Overview on page 29 Documentation Modules Supported on SRX1400, SRX3400, and SRX3600 Services Gateways on page 30 Eligible Slots for SRX1400, SRX3400, and SRX3600 Services Gateway Modules on...
The SRX1400 Services Gateway also includes an air filter that protects the device from dust entering into the system. The SRX1400 Services Gateway has one fan tray located in the side of the chassis and can be plugged in from the rear of the chassis.
Related Troubleshooting the Cooling System on the SRX1400 Services Gateway on page 161 Documentation Routine Maintenance Procedures for the SRX1400 Services Gateway on page 149...
Only redundant power supplies (AC or DC) support hot-swappable functionality. The SRX1400 Services Gateway uses either one AC or one DC power supply unit. A second AC or DC power supply can be used with its matching type of power supply to offer redundancy.
AC Power Supply Electrical Specifications on page 50 AC Power Supply LEDs on page 51 AC Power Supply Overview In an AC power configuration, the SRX1400 Services Gateway contains one or two AC power supplies, located at the front panel of the chassis in slots PEM0 PEM1 .
SRX1400 Services Gateway Power Supplies Overview on page 49 Documentation Installing an AC Power Supply in the SRX1400 Services Gateway on page 118 Maintaining Power Supplies on the SRX1400 Services Gateway on page 152 Troubleshooting the Power System on the SRX1400 Services Gateway on page 159...
SRX1400 Services Gateway Hardware Guide DC Power Supply Overview In a DC power configuration, the SRX1400 Services Gateway contains one or two DC power supplies, located at the front of the chassis in slots . Each power supply provides power to all components in the services gateway. When two power supplies are present, they share power almost equally within a fully populated system.
Page 77
SRX1400 Services Gateway Power Supplies Overview on page 49 Documentation Installing a DC Power Supply in the SRX1400 Services Gateway on page 119 Maintaining Power Supplies on the SRX1400 Services Gateway on page 152 Troubleshooting the Power System on the SRX1400 Services Gateway on page 159...
CHAPTER 7 Planning and Preparing the Site Site Preparation Checklist for the SRX1400 Services Gateway on page 57 SRX1400 Services Gateway Physical Specifications on page 58 SRX1400 Services Gateway Environmental Specifications on page 60 Site Preparation Checklist for the SRX1400 Services Gateway...
SRX1400 Services Gateway Rack Requirements on page 61 SRX1400 Services Gateway Physical Specifications The SRX1400 Services Gateway chassis is a rigid sheet metal structure that houses all of the other device components. The chassis measures 5.25 in. (13.3 cm) high, 17.5 in.
Fully configured chassis: 42.5 lb (19.3 kg) Table 25 on page 59 summarizes the weight of the SRX1400 Services Gateway chassis with different configurations. Table 25: Weight of the SRX1400 Services Gateway with Different Configurations SRX1400 Chassis with Different Configurations Weight Base chassis 29.3 lb (13.3 kg)
Connecting the SRX1400 Services Gateway to the Building Structure on page 63 SRX1400 Services Gateway Rack Size and Strength Requirements The SRX1400 Services Gateway can be installed in a rack. Many types of racks are acceptable, including four-post (telco) racks and open-frame racks.
Cabinets, Racks, Panels, and Associated Equipment (document number EIA-310-D) published by the Electronics Industry Association. You can stack eight SRX1400 Services Gateways in a rack that has at least 40 U (70 in. or 1.78 m) of usable vertical space.
Installation Overview for the SRX1400 Services Gateway on page 89 Documentation Site Preparation Checklist for the SRX1400 Services Gateway on page 57 SRX1400 Services Gateway Cabinet Requirements on page 65 Clearance Requirements for Airflow and Hardware Maintenance of the SRX1400...
CHAPTER 9 Cabinet Requirements SRX1400 Services Gateway Cabinet Requirements on page 65 SRX1400 Services Gateway Cabinet Requirements This topic includes the following sections: Cabinet Size and Clearance Requirements on page 65 Cabinet Airflow Requirements on page 65 Cabinet Size and Clearance Requirements The minimum size cabinet that can accommodate the services gateway is 27.5 in.
CHAPTER 10 Grounding Specifications SRX1400 Services Gateway Grounding-Cable Lug Specification on page 67 SRX1400 Services Gateway Grounding Cable Specification on page 67 SRX1400 Services Gateway Grounding-Cable Lug Specification The cable attaches to the grounding cable (see Figure 35 on page 67) and two M5 screws are used to secure the grounding cable to the grounding point.
“Grounding the SRX1400 Services Gateway” on page 123 for instructions. Related SRX1400 Services Gateway Chassis Grounding Point on page 121 Documentation SRX1400 Services Gateway Grounding-Cable Lug Specification on page 67 Grounding the SRX1400 Services Gateway on page 123 SRX1400 Services Gateway Front Panel on page 25...
Power Requirements for AC-Powered SRX1400 Services Gateways on page 72 SRX1400 Services Gateway AC Power Supply on page 50 Connecting the SRX1400 Services Gateway to an AC Power Supply on page 129 SRX1400 Services Gateway AC Power Cord Specifications Each AC power supply has a single AC appliance inlet located on the power supply that requires a dedicated AC power feed and a dedicated 15 A (250 VAC) circuit breaker.
Figure 36: AC Plug Types WARNING: The AC power cord for the services gateway is intended for use with the SRX1400 Services Gateway only and not for any other devices. WARNING: The attached power cable is only for this product. Do not use the cable for another product.
Power Requirements for AC-Powered SRX1400 Services Gateways on page 72 SRX1400 Services Gateway AC Power Supply on page 50 Connecting the SRX1400 Services Gateway to an AC Power Supply on page 129 Power Requirements for AC-Powered SRX1400 Services Gateways NOTE: If you plan to operate a maximally configured AC-powered services gateway, we recommend that you provision 6 A at 240 VAC for the system.
SRX1400 Services Gateway DC Power Cable Specifications on page 76 SRX1400 Services Gateway DC Power Supply on page 51 Installing a DC Power Supply in the SRX1400 Services Gateway on page 119 SRX1400 Services Gateway DC Power Supply Electrical Specifications Each DC power supply has a single DC input (-48 VDC and return) that requires a dedicated 16 A (-48 VDC) circuit breaker.
SRX1400 Services Gateway DC Power Cable Specifications on page 76 SRX1400 Services Gateway DC Power Supply on page 51 Installing a DC Power Supply in the SRX1400 Services Gateway on page 119 SRX1400 Services Gateway DC Power Cable Specifications The DC power supply in slot...
210 W to the overall system power requirement. NOTE: In the SRX1400 Services Gateways with 1-Gigabit Ethernet System I/O card, the base system power requirement is less by 5-6 watts than the SRX1400 devices with 10-Gigabit Ethernet System I/O card.
Console Port Cable and Wire Specifications for the SRX1400 Services Gateway on page 81 Signal Loss in Multimode and Single-Mode Fiber-Optic Cable for the SRX1400 Services Gateway on page 82 Calculating the Power Budget for Fiber-Optic Cable for the SRX1400 Services...
SRX1400 Services Gateway Hardware Guide Signal Loss in Multimode and Single-Mode Fiber-Optic Cable for the SRX1400 Services Gateway Multimode fiber is large enough in diameter to allow rays of light to reflect internally (bounce off the walls of the fiber). Interfaces with multimode optics typically use LEDs as light sources.
Related SRX1400 Services Gateway Electrical Wiring Guidelines on page 258 Documentation Signal Loss in Multimode and Single-Mode Fiber-Optic Cable for the SRX1400 Services Gateway on page 82 Attenuation and Dispersion in Fiber-Optic Cable for the SRX1400 Services Gateway on page 83...
SRX1400 Services Gateway Hardware Guide Calculating the Power Budget for Fiber-Optic Cable for the SRX1400 Services Gateway on page 82 Calculating the Power Margin for Fiber-Optic Cable for the SRX1400 Services Gateway on page 84 Calculating the Power Margin for Fiber-Optic Cable for the SRX1400 Services Gateway...
Related SRX1400 Services Gateway Electrical Wiring Guidelines on page 258 Documentation Signal Loss in Multimode and Single-Mode Fiber-Optic Cable for the SRX1400 Services Gateway on page 82 Attenuation and Dispersion in Fiber-Optic Cable for the SRX1400 Services Gateway on page 83...
Installation Overview on page 89 Unpacking the Services Gateway on page 93 Installing the Mounting Hardware on page 97 Installing the SRX1400 Services Gateway Using a Mechanical Lift on page 99 Installing the SRX1400 Services Gateway Manually (Without a Mechanical Lift) on page 103...
Installation on page 90 Installation Overview for the SRX1400 Services Gateway This section provides instructions for installing the SRX1400 Services Gateway in a rack or cabinet. Because of the size and weight of the device—up to 42.5 lb (19.3 kg) (fully loaded chassis) depending on the configuration—we recommend that you install it using...
Page 114
Documentation Installing the Mounting Hardware for the SRX1400 Services Gateway on page 97 Installing the SRX1400 Services Gateway in a Rack or Cabinet Using a Mechanical Lift on page 99 Installing the SRX1400 Services Gateway in a Rack or Cabinet Manually on page 106...
Verifying Parts Received with the SRX1400 Services Gateway on page 95 Required Tools and Parts for Unpacking the SRX1400 Services Gateway To unpack the SRX1400 Services Gateway and prepare for installation, you need a Phillips (+) screwdriver, number 2. Related...
95, and an accessory box, which contains the parts listed in Table 43 on page 96. The parts shipped with your services gateway can vary depending on the configuration you ordered. Table 42: Parts List for a Fully Configured SRX1400 Services Gateway Component Quantity Chassis, including backplane, and rack-mounting...
Gateway) on the SRX1400 device, then you must order them separately. You can use an NPC and an SPC on the SRX1400 device in place of the NSPC. To install the NPC and SPC on the SRX1400 Services Gateway, you must order the double-wide tray (SRX1K3K-2CFM-TRAY) to hold two single-wide CFMs (NPC and SPC) separately.
90 Installing the Mounting Hardware for the SRX1400 Services Gateway on page 97 Installing the SRX1400 Services Gateway in a Rack or Cabinet Using a Mechanical Lift on page 99 Removing Components from the Chassis for Manual Lifting of the SRX1400 Services...
This topic provides the installation instructions on front-mounting of the device in a two-post rack. To install an SRX1400 Services Gateway in a rack or cabinet: Ensure the rack is in its permanent location and is secured to the building.
Chapter 17: Installing the SRX1400 Services Gateway Using a Mechanical Lift Figure 40: Attach Mounting Hardware for Two-Post Rack For front-mounting the chassis in a two-post rack, align the bottom hole in each mounting bracket at the front edge of the chassis.
Gateway on page 104 Lifting the SRX1400 Services Gateway Chassis into a Rack on page 104 Installing the SRX1400 Services Gateway in a Rack or Cabinet Manually on page 106 Reinstalling Components into the SRX1400 Services Gateway Chassis on page 107...
To remove the components from the services gateway: Attach an ESD grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis. For more information about ESD, see the SRX1400 Services Gateway hardware documentation at www.juniper.net/techpubs...
Chapter 18: Installing the SRX1400 Services Gateway Manually (Without a Mechanical Lift) Figure 41: Lift the Chassis Into the Rack Align the bottom hole in each mounting bracket with a hole in each rack rail as shown Figure 42 on page 105.
Reinstalling Components into the SRX1400 Services Gateway Chassis on page 107 Installing the SRX1400 Services Gateway in a Rack or Cabinet Manually If you cannot use a mechanical lift to install the SRX1400 Services Gateway (the preferred method), you can install it manually. Before installing the services gateway manually, you must first remove components from the chassis, and you must reinstall the components once the services gateway is installed in the rack.
Chapter 18: Installing the SRX1400 Services Gateway Manually (Without a Mechanical Lift) Reinstall the components into the SRX1400 Services Gateway chassis. For more information, see “Reinstalling Components into the SRX1400 Services Gateway Chassis” on page 107. Related SRX1400 Services Gateway Safety Requirements, Warnings, and Guidelines on page 223...
Installing an SPC in an SRX1400 Services Gateway on page 111 Installing an NPC in an SRX1400 Services Gateway on page 113 Installing an IOC or NP-IOC in an SRX1400 Services Gateway on page 115 Installing a System I/O Card into the SRX1400 Services Gateway on page 117...
Figure 43 on page 110) to shield the empty slots and to allow cooling air to circulate properly through the device. Figure 43: SRX1400 Services Gateway with CFM Slots 1 and 3 Covered by Double-Wide Filler Cover To install an NSPC: Attach an ESD grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
SRX1400 Services Gateway Hardware Components on page 9 Installing an SPC in an SRX1400 Services Gateway There are two places where you can install an SPC in your SRX1400 Services Gateway: You can install an SPC in the front-panel slot labeled...
Chapter 19: Installing Additional Hardware Components Figure 47: Installing an SPC in Slot 2 of the SRX1400 Services Gateway Tighten the screws on either side of the card. You can proceed with installing other hardware components or power supplies, or connecting to a management device.
SRX1400 Services Gateway Hardware Guide NOTE: To install the NPC and SPC on the SRX1400 Services Gateway, you must order the double-wide tray (SRX1K3K-2CFM-TRAY) to hold the two single-wide CFMs (NPC and SPC) separately. Contact your Juniper Networks customer service representative for more information.
Troubleshooting an NPC on the SRX1400 Services Gateway on page 164 Installing an IOC or NP-IOC in an SRX1400 Services Gateway You can install an IOC or NP-IOC in slot 2 on the SRX1400 Services Gateway front panel. “SRX1400 Services Gateway Front Panel” on page 25 for front panel slot locations.
Page 140
CAUTION: If you are having a problem running a Juniper Networks device that is using a third-party optic or cable, the Juniper Networks Technical Assistance Center (JTAC) can help you diagnose the source of the problem. Your JTAC engineer might recommend that you check the third-party optic or cable and potentially replace it with an equivalent Juniper Networks optic or cable that is qualified for the device.
Related SRX1400 Services Gateway Hardware Components on page 9 Documentation Installing a System I/O Card into the SRX1400 Services Gateway Before installing your card, see “SRX1400 Services Gateway Front Panel” on page 25 verify that you have selected an appropriate slot location.
Documentation SRX1400 Services Gateway Hardware Components on page 9 Installing an AC Power Supply in the SRX1400 Services Gateway on page 118 Installing a DC Power Supply in the SRX1400 Services Gateway on page 119 Installing an AC Power Supply in the SRX1400 Services Gateway...
Documentation SRX1400 Services Gateway AC Power Supply on page 50 Installing a DC Power Supply in the SRX1400 Services Gateway on page 119 Connecting the SRX1400 Services Gateway to an AC Power Supply on page 129 Installing a DC Power Supply in the SRX1400 Services Gateway...
CHAPTER 20 Grounding the SRX1400 Services Gateway Required Tools and Parts for Grounding and Providing Power to the SRX1400 Services Gateway on page 121 SRX1400 Services Gateway Chassis Grounding Point on page 121 Grounding the SRX1400 Services Gateway on page 123...
M5 screws used to secure the grounding cable to the services gateway grounding point. Figure 52: Grounding Point on the SRX1400 Services Gateway To ground the services gateway, you must connect a grounding cable to earth ground and then attach it to the chassis grounding point using the two screws provided.
Chapter 20: Grounding the SRX1400 Services Gateway Grounding the SRX1400 Services Gateway WARNING: To meet safety and electromagnetic interference (EMI) requirements and to ensure proper operation, you must properly ground the services gateway chassis before connecting power. CAUTION: Before you connect power to the services gateway, a licensed electrician must attach a cable lug to the grounding cable that you use.
Dress the grounding cable, and verify that it does not touch or block access to device components and it does not cause a tripping hazard. Related Required Tools and Parts for Grounding and Providing Power to the SRX1400 Services Documentation Gateway on page 121...
CHAPTER 21 Connecting the SRX1400 Services Gateway to External Devices Connecting the SRX1400 Services Gateway to a Management Console or an Auxiliary Device on page 125 Connecting the SRX1400 Services Gateway to a Network for Out-of-Band Management on page 126...
Stop bits—1 Flow control—none Proceed with grounding and powering on the device. You can start performing initial software configuration on the SRX1400 Services Gateway after the device is up. Related Connecting the SRX1400 Services Gateway to a Network for Out-of-Band Management...
Page 151
Plug the other end of the cable into the management device. Proceed with grounding and powering on the device. Related Connecting the SRX1400 Services Gateway to a Management Console or an Auxiliary Documentation Device on page 125 SRX1400 Services Gateway Software Configuration Overview on page 137...
Providing Power to the SRX1400 Services Gateway Connecting the SRX1400 Services Gateway to an AC Power Supply on page 129 Connecting the SRX1400 Services Gateway to a DC Power Supply on page 132 Powering On the SRX1400 Services Gateway on page 133...
SRX1400 Services Gateway Hardware Guide a. Insert the appliance coupler end of the power cord into the appliance inlet on the power supply. b. Snap the wire bail on the power supply over the power cord to prevent the power cord from accidentally disengaging.
Page 155
For example, if the services gateway loses power while the device is on, when power returns, the device will still be in the On state. Related Required Tools and Parts for Grounding and Providing Power to the SRX1400 Services Documentation Gateway on page 121...
SRX1400 Services Gateway Hardware Guide Connecting the SRX1400 Services Gateway to a DC Power Supply You connect DC power to the services gateway by attaching power cables from the external DC power sources to the terminal studs on the power supply faceplates.
For example, if the services gateway loses power while the device is on, when power returns, the device will still be in the On state. Related Required Tools and Parts for Grounding and Providing Power to the SRX1400 Services Documentation Gateway on page 121...
On state. Related Connecting the SRX1400 Services Gateway to an AC Power Supply on page 129 Documentation Connecting the SRX1400 Services Gateway to a DC Power Supply on page 132...
CHAPTER 23 Performing the Initial Configuration SRX1400 Services Gateway Software Configuration Overview on page 137 Performing Initial Software Configuration on the SRX1400 Services Gateway (CLI Procedure) on page 138 Performing Initial Software Configuration Using J-Web on page 142 SRX1400 Services Gateway Software Configuration Overview The services gateway is shipped with Junos OS preinstalled and ready to be configured when the services gateway is powered on.
Connecting the SRX1400 Services Gateway to a Network for Out-of-Band Management Documentation on page 126 Connecting the SRX1400 Services Gateway to a Management Console or an Auxiliary Device on page 125 Performing Initial Software Configuration on the SRX1400 Services Gateway (CLI...
Page 164
SRX1400 Services Gateway Hardware Guide Optionally, display the configuration to verify that it is correct. NOTE: This is a sample output. The actual output might vary depending on your configuration requirements. admin@# show ## Last changed: 2010-08-18 05:50:46 UTC version "10.4I0 [sharibkh]";...
Connecting the SRX1400 Services Gateway to a Network for Out-of-Band Management Documentation on page 126 Connecting the SRX1400 Services Gateway to a Management Console or an Auxiliary Device on page 125 SRX1400 Services Gateway Software Configuration Overview on page 137...
SRX1400 Services Gateway Hardware Guide Configuring the Hostname To configure the hostname: Launch a Web browser from the management device. Enter the IP address of the device in the URL address field. Specify the default username as root and enter the password. See “Configuring Root...
A message appears after your configuration changes are applied successfully. Click You have successfully configured the security policy. Related Performing Initial Software Configuration on the SRX1400 Services Gateway (CLI Documentation Procedure) on page 138 Performing Initial Software Configuration on the SRX3400 Services Gateway...
Components on page 149 Routine Maintenance Procedures for the SRX1400 Services Gateway on page 149 Maintaining the Air Filter on the SRX1400 Services Gateway on page 150 Maintaining the Fan Tray on the SRX1400 Services Gateway on page 150 Maintaining the Routing Engine on the SRX1400 Services Gateway on page 151...
Components on page 149 Maintaining Power Supplies on the SRX1400 Services Gateway on page 152 Maintaining the Fan Tray on the SRX1400 Services Gateway on page 150 Maintaining the Air Filter on the SRX1400 Services Gateway on page 150 Maintaining the Air Filter on the SRX1400 Services Gateway A dirty air filter restricts airflow in the unit, reducing the ventilation of the chassis.
Components on page 149 Routine Maintenance Procedures for the SRX1400 Services Gateway on page 149 Maintaining the Air Filter on the SRX1400 Services Gateway on page 150 Replacing the Fan Tray on the SRX1400 Services Gateway on page 191 Maintaining the Routing Engine on the SRX1400 Services Gateway...
Spinning at normal speed For more information about using the CLI, see the CLI Explorer Related Required Tools and Parts for Maintaining the SRX1400 Services Gateway Hardware Documentation Components on page 149 Routine Maintenance Procedures for the SRX1400 Services Gateway on page 149...
Troubleshooting the Power System on the SRX1400 Services Gateway on page 159 Troubleshooting the Cooling System on the SRX1400 Services Gateway on page 161 Troubleshooting the System I/O Card on the SRX1400 Services Gateway on page 162 Troubleshooting the Network and Services Processing Card on the SRX1400 Services...
Page 180
SRX1400 Services Gateway Hardware Guide Online 1024 Online 1024 Online 1024 Using a question mark (?) gives you a listing of the various options for the command as shown below: user@host> show chassis fpc ? Possible completions: <[Enter]> Execute this command <fpc-slot>...
Troubleshooting the Cooling System on the SRX1400 Services Gateway on page 161 Troubleshooting the System I/O Card on the SRX1400 Services Gateway on page 162 Troubleshooting the Network and Services Processing Card on the SRX1400 Services...
Interface alarms—Indicate a problem with a specific network interface. Related Troubleshooting with the CLI on the SRX1400 Services Gateway on page 155 Documentation Troubleshooting with LEDs on the SRX1400 Services Gateway on page 157 Juniper Networks Technical Assistance Center...
Page 184
Verify that the Routing Engine, SYSIOC, and at least one power supply is installed on the SRX1400 Services Gateway and are functioning properly; otherwise the device can not be powered on. Verify that the source circuit breaker has the proper current rating. Each power supply must be connected to a separate source circuit breaker.
Documentation SRX1400 Services Gateway DC Power Supply on page 51 Replacing an AC Power Supply on the SRX1400 Services Gateway on page 198 Replacing AC Power Supply Cables on the SRX1400 Services Gateway on page 197 Replacing a DC Power Supply on the SRX1400 Services Gateway on page 201...
SRX1400 Services Gateway Cooling System on page 47 Documentation Maintaining the Fan Tray on the SRX1400 Services Gateway on page 150 Maintaining the Air Filter on the SRX1400 Services Gateway on page 150 Troubleshooting the System I/O Card on the SRX1400 Services Gateway To troubleshoot a SYSIOC , follow these guidelines: Make sure the SYSIOC is properly seated in the slot and its screws are tightened.
DRAM (MB) Heap Buffer Online 1024 NOTE: Because the NSPC occupies slot 1 and slot 3 of the SRX1400 Services Gateway chassis, you can use the show chassis fpc 1 commands to check the status of NSPC. show chassis fpc 3 Use the CLI show chassis fpc 1 detail command for more detailed output.
For further descriptions of the output from the commands, see the Junos System Basics and Services Command Reference. Related Replacing an IOC or NP-IOC on the SRX1400 Services Gateway on page 180 Documentation Juniper Networks Technical Assistance Center Troubleshooting an NPC on the SRX1400 Services Gateway...
Troubleshooting Services Processing Cards on the SRX1400 Services Gateway There are two places an SPC can be installed in your SRX1400 Services Gateway: You can install an SPC in the front-panel slot labeled 1 if you also install an NPC in the slot labeled 3.
CHAPTER 26 Overview of Replacing Components Required Tools and Parts for Replacing Hardware Components on the SRX1400 Services Gateway on page 169 Field-Replaceable Units on the SRX1400 Services Gateway on page 170 Required Tools and Parts for Replacing Hardware Components on the SRX1400...
NSPC SFP, SFP+, and XFP transceivers NP-IOC Related Required Tools and Parts for Replacing Hardware Components on the SRX1400 Documentation Services Gateway on page 169 SRX1400 Services Gateway Hardware Components on page 9 SRX1400 Services Gateway Front Panel on page 25...
Replacing SFP, SFP+, and XFP Transceivers on the SRX1400 Services Gateway on page 173 Replacing SFP, SFP+, and XFP Transceivers on the SRX1400 Services Gateway Small form-factor pluggable (SFP), enhanced small form-factor pluggable (SFP+), and 10-Gigabit SFP (XFP) are transceivers that you install in sockets in various cards or modules in the services gateway.
SRX1400 Services Gateway Hardware Guide Carefully drape the disconnected cables to prevent the cable from developing stress points. CAUTION: Avoid bending fiber-optic cable beyond its minimum bend radius. An arc smaller than a few inches in diameter can damage the cable and cause problems that are difficult to diagnose.
Replacing Host Subsystem Components Replacing a Routing Engine on the SRX1400 Services Gateway on page 177 Replacing an IOC or NP-IOC on the SRX1400 Services Gateway on page 180 Replacing a Network and Services Processing Card on the SRX1400 Services...
Press both of the ejector handles inward to seat the Routing Engine. See Figure 60 on page 178. Figure 60: Installing the Routing Engine on the SRX1400 Services Gateway Tighten the captive screws on the left and right of the Routing Engine. Reconnect cables previously attached to the AUX or USB ports.
Services Gateway on page 169 SRX1400 Services Gateway Routing Engine on page 19 Maintaining the Routing Engine on the SRX1400 Services Gateway on page 151 Field-Replaceable Units on the SRX1400 Services Gateway on page 170 Replacing an IOC or NP-IOC on the SRX1400 Services Gateway...
Grasp the IOC or NP-IOC by its handle and slide it halfway out of the chassis. See Figure 61 on page 181. Figure 61: Removing an IOC or NP-IOC from the SRX1400 Services Gateway Place one hand underneath the IOC or NP-IOC to support it and slide it completely out of the chassis.
Tighten the captive screws on the left and right of the IOC or NP-IOC faceplate. See Figure 62 on page 182. Figure 62: Installing an IOC or NP-IOC on the SRX1400 Services Gateway If the IOC or NP-IOC uses fiber-optic cable, remove the rubber safety cap from each transceiver and cable.
Field-Replaceable Units on the SRX1400 Services Gateway on page 170 Replacing a Network and Services Processing Card on the SRX1400 Services Gateway The NSPC is installed on the front panel of the SRX1400 Services Gateway. NOTE: It is not necessary to power off the device to remove or replace the NSPC.
SRX1400 Services Gateway Hardware Guide Figure 63: Removing the NSPC from the SRX1400 Services Gateway Grasp the NSPC by the ejector handles and slide it halfway out of the chassis. Place one hand underneath the NSPC to support it and slide it completely out of the chassis.
Field-Replaceable Units on the SRX1400 Services Gateway on page 170 Replacing the SYSIOC on the SRX1400 Services Gateway The system I/O card (SYSIOC) is installed in the front of the SRX1400 Services Gateway. To replace the SYSIOC: If you have not already done so, power off the services gateway as described in “Powering Off the SRX1400 Services Gateway”...
Figure 66 on page 186. Figure 66: Installing the SYSIOC from the SRX1400 Services Gateway Tighten the captive screws on the left and right of the SYSIOC faceplate. Insert the appropriate cables into the cable connector ports on each SYSIOC.
Services Gateway on page 169 SRX1400 Services Gateway SYSIOCs on page 12 Troubleshooting the System I/O Card on the SRX1400 Services Gateway on page 162 Field-Replaceable Units on the SRX1400 Services Gateway on page 170 Replacing a Network Processing Card on the SRX1400 Services Gateway...
SRX1400 Services Gateway Hardware Guide Figure 67: Removing an NPC from the SRX1400 Services Gateway SRX 3K- SPC -1-1 0-40 SRX 3K- NPC Place one hand underneath the NPC to support it and slide it completely out of the chassis.
Field-Replaceable Units on the SRX1400 Services Gateway on page 170 Replacing an SPC on the SRX1400 Services Gateway There are two places an SPC can be installed in your SRX1400 Services Gateway: You can install an SPC in the front-panel slot labeled...
SPCs or other CFM cards. The handles might come off, causing the chassis to drop and inflicting possible grave injury. Related Required Tools and Parts for Replacing Hardware Components on the SRX1400 Documentation Services Gateway on page 169...
Replacing the Fan Tray on the SRX1400 Services Gateway The SRX1400 Services Gateway has one fan tray located in the side of the chassis and can be plugged in from the rear of the chassis. The fan tray contains two fans. The fan tray supports hot-swappable functionality.
Attach an ESD grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis. For more information about ESD, see “Preventing Electrostatic Discharge Damage to the SRX1400 Services Gateway” on page 226. Turn the screw to the left on the fan tray door as shown in Figure 71 on page 192.
Chapter 29: Replacing Cooling System Components Figure 72: Removing the Fan Tray from the SRX1400 Services Gateway Grasp the fan tray and pull it out approximately 6 in. (15 cm). Place one hand under the fan tray to support it and pull the fan tray completely out of the chassis.
Services Gateway on page 169 SRX1400 Services Gateway Cooling System on page 47 Troubleshooting the Cooling System on the SRX1400 Services Gateway on page 161 Maintaining the Fan Tray on the SRX1400 Services Gateway on page 150 Replacing the Cooling System Air Filter on the SRX1400 Services Gateway...
Turn the screw to the left on the fan tray door. Open it to the right and remove it. See Figure 74 on page 195 Figure 74: Removing the Cooling System Air Filter from the SRX1400 Services Gateway Slide the air filter out of the chassis and properly dispose of it.
Replacing a DC Power Supply on the SRX1400 Services Gateway on page 201 Replacing DC Power Supply Cables on the SRX1400 Services Gateway on page 204 Replacing the Power Supply Air Filter on the SRX1400 Services Gateway on page 205 Replacing AC Power Supply Cables on the SRX1400 Services Gateway...
Required Tools and Parts for Replacing Hardware Components on the SRX1400 Documentation Services Gateway on page 169 Replacing an AC Power Supply on the SRX1400 Services Gateway on page 198 SRX1400 Services Gateway AC Power Supply on page 50 Maintaining Power Supplies on the SRX1400 Services Gateway on page 152...
See Figure 78 on page 199. Figure 78: Installing an AC Power Supply in the SRX1400 Services Gateway CAUTION: Do not mix AC and DC power supplies within the same services gateway. Damage to the device might occur.
Pull the power supply straight out of the chassis. See figure Figure 79 on page 201. Figure 79: Removing a DC Power Supply from the SRX1400 Services Gateway Orient the replacement power supply so that the tab is on the left side, as shown in Figure 80 on page 202.
SRX1400 Services Gateway Hardware Guide Figure 80: Installing a DC Power Supply on the SRX1400 Services Gateway Using both hands, slide the replacement power supply straight into the chassis until the power supply is fully seated in the chassis slot. Make sure the tab on the left edge of the power supply clicks into place.
Chapter 30: Replacing Power Supply Components Figure 81: Typical DC Source Cabling to the SRX1400 Services Gateway Front panel of SRX1400 CAUTION: You must ensure that power connections maintain the proper polarity. The power source cables might be labeled to indicate (–)
Required Tools and Parts for Replacing Hardware Components on the SRX1400 Documentation Services Gateway on page 169 Replacing DC Power Supply Cables on the SRX1400 Services Gateway on page 204 SRX1400 Services Gateway DC Power Supply on page 51 Maintaining Power Supplies on the SRX1400 Services Gateway on page 152...
Troubleshooting the Power System on the SRX1400 Services Gateway on page 159 Replacing the Power Supply Air Filter on the SRX1400 Services Gateway The SRX1400 Services Gateway power supply has one air filter located in the front of the power supply. The SRX1400 power supply air filter supports hot-swappable functionality.
To replace the air filter: Attach an ESD grounding strap to your bare wrist and connect the strap to one of the ESD points on the SRX1400 chassis. For more information about ESD, see “Preventing Electrostatic Discharge Damage to the SRX1400 Services Gateway” on page 226.
Locating the SRX1400 Services Gateway Routing Engine Serial Number Label on page 213 Locating the SRX1400 Services Gateway Power Supply Serial Number Label on page 214 Locating the SRX1400 Services Gateway Fan Tray Number Label on page 214 Information You Might Need to Supply to JTAC on page 215...
To return a services gateway or component to Juniper Networks for repair or replacement: Determine the part number and serial number of the services gateway or component. For the serial number locations of CFMs (SPCs, IOCs, and NPCs), see the...
Chapter 31: Contacting Customer Support Related Listing the SRX1400 Services Gateway Component Serial Numbers with the CLI on Documentation page 211 Information You Might Need to Supply to JTAC on page 215 Contacting Customer Support on page 209 Packing the SRX1400 Services Gateway for Shipment on page 216...
Related Return Procedure for the SRX1400 Services Gateway on page 210 Documentation Listing the SRX1400 Services Gateway Component Serial Numbers with the CLI on page 211 Information You Might Need to Supply to JTAC on page 215 Contacting Customer Support on page 209...
Related Return Procedure for the SRX1400 Services Gateway on page 210 Documentation Listing the SRX1400 Services Gateway Component Serial Numbers with the CLI on page 211 Information You Might Need to Supply to JTAC on page 215 Contacting Customer Support on page 209...
Related Return Procedure for the SRX1400 Services Gateway on page 210 Documentation Listing the SRX1400 Services Gateway Component Serial Numbers with the CLI on page 211 Information You Might Need to Supply to JTAC on page 215 Contacting Customer Support on page 209...
Related Return Procedure for the SRX1400 Services Gateway on page 210 Documentation Listing the SRX1400 Services Gateway Component Serial Numbers with the CLI on page 211 Information You Might Need to Supply to JTAC on page 215 Contacting Customer Support on page 209...
To pack the services gateway for shipment: Retrieve the shipping carton and packing materials in which the services gateway was originally shipped. If you do not have these materials, contact your Juniper Networks representative about approved packaging materials. Attach an ESD grounding strap to your bare wrist and connect the strap to the ESD point on the chassis or to an outside ESD point if the services gateway is disconnected from earth ground.
Information You Might Need to Supply to JTAC on page 215 Contacting Customer Support on page 209 Required Tools and Parts for Packing the SRX1400 Services Gateway on page 216 Packing SRX1400 Services Gateway Components for Shipment on page 217...
CHAPTER 32 General Safety Guidelines and Warnings SRX1400 Services Gateway Definition of Safety Warning Levels on page 221 SRX1400 Services Gateway Safety Requirements, Warnings, and Guidelines on page 223 SRX1400 Services Gateway General Safety Guidelines and Warnings on page 223...
Installing the Mounting Hardware for the SRX1400 Services Gateway on page 97 Documentation Installing the SRX1400 Services Gateway in a Rack or Cabinet Using a Mechanical Lift on page 99 Installing the SRX1400 Services Gateway in a Rack or Cabinet Manually on page 106...
Avoid touching uninsulated electrical wires or terminals that have not been disconnected from their power source. Such an action could cause electrical shock. Related SRX1400 Services Gateway Definition of Safety Warning Levels on page 221 Documentation Qualified Personnel Warning on page 224...
Chapter 32: General Safety Guidelines and Warnings Related SRX1400 Services Gateway Definition of Safety Warning Levels on page 221 Documentation SRX1400 Services Gateway General Safety Guidelines and Warnings on page 223 Restricted Access Area Warning on page 225 Preventing Electrostatic Discharge Damage to the SRX1400 Services Gateway on...
Related SRX1400 Services Gateway Definition of Safety Warning Levels on page 221 Documentation SRX1400 Services Gateway General Safety Guidelines and Warnings on page 223 Qualified Personnel Warning on page 224...
SRX1400 Services Gateway Fire Safety Requirements and Fire Suppression Equipment on page 229 SRX1400 Services Gateway Fire Safety Requirements and Fire Suppression Equipment In the event of a fire emergency involving services gateways and other network equipment, the safety of people is the primary concern. Establish procedures for protecting people in the event of a fire emergency, provide safety training, and properly provision fire control equipment and fire extinguishers.
Page 254
To keep warranties effective, do not use a dry chemical fire extinguisher to control a fire at or near a Juniper Networks services gateway. If a dry chemical fire extinguisher is used, the unit is no longer eligible for coverage under a service agreement.
Before moving the services gateway, read the guidelines in the following topics to verify that the intended site meets the specified power, environmental, and clearance requirements: Site Preparation Checklist for the SRX1400 Services Gateway on page 57 SRX1400 Services Gateway Cabinet Requirements on page 65 SRX1400 Services Gateway Rack Requirements on page 61...
Related Chassis Lifting Guidelines on page 231 Documentation SRX1400 Services Gateway General Safety Guidelines and Warnings on page 223 Rack-Mounting Requirements and Warnings on page 232 Ramp Warning on page 236 Rack-Mounting Requirements and Warnings Ensure that the equipment rack into which the services gateway is installed is evenly and securely supported to avoid the hazardous condition that could result from uneven mechanical loading.
Page 257
De onderstaande richtlijnen worden verstrekt om uw veiligheid te verzekeren: De Juniper Networks services gateway moet in een stellage worden geïnstalleerd die aan een bouwsel is verankerd. Dit toestel dient onderaan in het rek gemonteerd te worden als het toestel het enige in het rek is.
Page 258
Les directives ci-dessous sont destinées à assurer la protection du personnel: Le rack sur lequel est monté le Juniper Networks services gateway doit être fixé à la structure du bâtiment. Si cette unité constitue la seule unité montée en casier, elle doit être placée dans le bas.
Page 259
Vær nøye med at systemet er stabilt. Følgende retningslinjer er gitt for å verne om sikkerheten: Juniper Networks services gateway må installeres i et stativ som er forankret til bygningsstrukturen. Denne enheten bør monteres nederst i kabinettet hvis dette er den eneste enheten i kabinettet.
Related Chassis Lifting Guidelines on page 231 Documentation Installation Instructions Warning on page 232 SRX1400 Services Gateway General Safety Guidelines and Warnings on page 223 Ramp Warning on page 236 Ramp Warning WARNING: When installing the services gateway, do not use a ramp inclined at more than 10 degrees.
Class 1 LED Product Warning on page 240 Laser Beam Warning on page 241 Radiation from Open Port Apertures Warning on page 242 SRX1400 Services Gateway General Safety Guidelines and Warnings on page 223 Class 1 LED Product Warning WARNING: Class 1 LED product.
Class 1 Laser Product Warning on page 240 Laser Beam Warning on page 241 Radiation from Open Port Apertures Warning on page 242 SRX1400 Services Gateway General Safety Guidelines and Warnings on page 223 Laser Beam Warning WARNING: Do not stare into the laser beam or view it directly with optical instruments.
SRX1400 Services Gateway Hardware Guide SRX1400 Services Gateway General Safety Guidelines and Warnings on page 223 Radiation from Open Port Apertures Warning WARNING: Because invisible radiation might be emitted from the aperture of the port when no fiber cable is connected, avoid exposure to radiation and do not stare into open apertures.
Lightning Activity Warning on page 248 Operating Temperature Warning on page 249 Product Disposal Warning on page 248 SRX1400 Services Gateway General Safety Guidelines and Warnings on page 223 Jewelry Removal Warning WARNING: Before working on equipment that is connected to power lines, remove jewelry, including rings, necklaces, and watches.
SRX1400 Services Gateway Hardware Guide SRX1400 Services Gateway General Safety Guidelines and Warnings on page 223 Lightning Activity Warning WARNING: Do not work on the system or connect or disconnect cables during periods of lightning activity. Waarschuwing Tijdens onweer dat gepaard gaat met bliksem, dient u niet aan het systeem te werken of kabels aan te sluiten of te ontkoppelen.
Jewelry Removal Warning on page 246 Lightning Activity Warning on page 248 Operating Temperature Warning on page 249 SRX1400 Services Gateway General Safety Guidelines and Warnings on page 223 Operating Temperature Warning WARNING: To prevent the services gateway from overheating, do not operate it in an area that exceeds the maximum recommended ambient temperature of 104°F (40°C).
Page 274
40°C. Ettei ilmanvaihto estyisi, tuuletusaukkojen ympärille on jätettävä ainakin 15,2 cm tilaa. Attention Pour éviter toute surchauffe des routeurs de la gamme Juniper Networks services gateway, ne l'utilisez pas dans une zone où la température ambiante est supérieure à 40°C. Pour permettre un flot d'air constant, dégagez un espace d'au moins 15,2 cm autour des ouvertures de ventilations.
General Electrical Safety Guidelines and Warnings on page 253 Documentation DC Power Electrical Safety Guidelines and Warnings on page 259 SRX1400 Services Gateway General Safety Guidelines and Warnings on page 223 General Electrical Safety Guidelines and Warnings This topic includes the following sections:...
SRX1400 Services Gateway Hardware Guide Safety Guidelines and Warnings Install the services gateway in compliance with the following local, national, or international electrical codes: United States—National Fire Protection Association (NFPA 70), United States National Electrical Code Canada—Canadian Electrical Code, Part 1, CSA C22.1 Other countries—International Electromechanical Commission (IEC) 60364, Part 1...
SRX1400 Services Gateway Hardware Guide Aviso Este dispositivo possui mais do que uma conexão de fonte de alimentação de energia; para poder remover a fonte de alimentação de energia, deverão ser desconectadas todas as conexões existentes. ¡Atención! Esta unidad tiene más de una conexión de suministros de alimentación;...
SRX1400 Services Gateway Electrical Wiring Guidelines This topic includes the following sections: Distance Limitations for Signaling for the SRX1400 Services Gateway on page 258 Radio Frequency Interference for the SRX1400 Services Gateway on page 258 Electromagnetic Compatibility for the SRX1400 Services Gateway on page 258 Distance Limitations for Signaling for the SRX1400 Services Gateway Improperly installed wires can emit radio interference.
The addition of primary protectors is not sufficient protection for connecting these interfaces metallically to OSP wiring. Related Signal Loss in Multimode and Single-Mode Fiber-Optic Cable for the SRX1400 Services Documentation Gateway on page 82 Attenuation and Dispersion in Fiber-Optic Cable for the SRX1400 Services Gateway...
SRX1400 Services Gateway Hardware Guide A DC-powered services gateway is equipped with a DC terminal block that is rated for the power requirements of a maximally configured services gateway. To supply sufficient power, terminate the DC input wiring on a facility DC source capable of supplying at least 30 A @ -48 VDC for the system.
SRX1400 Services Gateway Hardware Guide y sujetar con cinta la palanca del interruptor automático en posición de Apagado (OFF). Varning! Innan du utför någon av följande procedurer måste du kontrollera att strömförsörjningen till likströmskretsen är bruten. Kontrollera att all strömförsörjning är BRUTEN genom att slå AV det överspänningsskydd som skyddar likströmskretsen och tejpa fast överspänningsskyddets omkopplare...
SRX1400 Services Gateway Hardware Guide Observe que el alambre de tierra se debe conectar siempre primero y desconectar por último. ¡Atención! Wire a fonte de alimentação de DC Usando os talões apropriados na extremidade da fiação. Ao conectar a potência, a seqüência apropriada da fiação é...
Agency Approvals and Regulatory Compliance Information SRX1400 Services Gateway Agency Approvals on page 267 SRX1400 Services Gateway Compliance Statements for EMC Requirements on page 268 SRX1400 Services Gateway NEBS and ETSI Compliance on page 269 SRX1400 Services Gateway Agency Approvals...
Page 298
SRX1400 Services Gateway Hardware Guide DC power cables hardware components replacing.................204 power requirements............72 DC power supply higher-order mode loss (HOL)..........82 installing................119 hot-swappable functionality of components, dispersion in fiber-optic cable...........83 description................170 documentation comments on..............xxi installation AC power, connecting..........129 earthquakes DC power, connecting..........132...