Replacing a System I/O Card on the SRX1400 Services Gateway

Copyright © 2011, Juniper Networks, Inc.
Chapter 13: Replacing Hardware Components on the SRX1400 Services Gateway
The system I/O card (SYSIOC) is installed in the front of the SRX1400 Services Gateway.
To replace a SYSIOC:
Place an electrostatic bag or antistatic mat on a flat, stable surface.
1.
Attach an ESD grounding strap to your bare wrist and connect the strap to one of the
2.
ESD points on the chassis. For more information about ESD, see "Preventing
Electrostatic Discharge Damage to the SRX1400 Services Gateway" on page 149.
Disconnect any cables attached to the console or management ports.
3.
Loosen the captive screws at each end of the SYSIOC faceplate.
4.
Pull open the ejector handles to unseat the SYSIOC.
5.
Grasp the SYSIOC by the ejector handles and slide it halfway out of the chassis. See
6.
figure Figure 43 on page 127
Figure 43: Removing the SYSIOC from the SRX1400 Services Gateway
Place one hand underneath the SYSIOC to support it and slide it completely out of
7.
the chassis.
Place the SYSIOC on the antistatic mat.
8.
We strongly recommend to reinstall the SYSIOC into the emptied slot as soon as the
replacement card is ready, in order to protects the device from dust entering into the
system through empty slot.
Carefully align the sides of the replacement SYSIOC with the guides inside the chassis.
9.
Slide the SYSIOC into the chassis until you feel resistance.
10.
Press both of the ejector handles inward to seat the SYSIOC as shown in Figure 44
11.
on page 128.