Replacing Cooling System Components on the SRX1400 Services Gateway

When the airflow through the chassis is inhibited because of a clogged filter or a fan
failure, you must replace the respective component. The cooling system components
support online insertion and removal.
The following topics provide instructions on how to replace these components:

Replacing the Fan Tray on the SRX1400 Services Gateway

The SRX1400 Services Gateway has one fan tray located in the side of the chassis and
can be plugged in from the rear of the chassis. The fan tray contains two fans. The fan
tray supports online insertion and removal. It weighs about 4.2 lb (1.9 kg).
You can also use the fan tray LED to detect the condition when the fan speed has reduced
to a safer value, so that the fan tray can be removed from the device safely.
Table 37 on page 116 provides the LED indications of the fan tray LED.
Copyright © 2011, Juniper Networks, Inc.
Chapter 13: Replacing Hardware Components on the SRX1400 Services Gateway
Tool or Part
Wire cutters
Field-Replaceable Units on the SRX1400 Services Gateway on page 113
SRX1400 Services Gateway Hardware Components on page 13
SRX1400 Services Gateway Front Panel on page 14
Overview of the SRX1400 Services Gateway Common Form-Factor Modules on page 11
Replacing the Fan Tray on the SRX1400 Services Gateway on page 115
Replacing the Cooling System Air Filter on the SRX1400 Services Gateway on page 118
NOTE: To prevent overheating, install the replacement fan tray immediately
after removing the existing fan tray. We recommend that you reinstall the
fan tray within 3 minutes; otherwise, the services gateway temperature
exceeds the maximum recommended room temperature, and the device
shuts down automatically in 4 minutes.
Components
Cables and connectors
DC power supply
115