Goodrive350 series high-performance multifunction VFD
Function
Name
code
motor 2
Direct-axis
inductance of
P12.21
synchronous
motor 2
Quadrature-axis
inductance of
P12.22
synchronous
motor 2
Counter-emf
constant of
P12.23
synchronous
motor 2
P12.24
Reserved
P12.25
Reserved
Overload
P12.26
protection of
motor 2
Overload
protection
P12.27
coefficient of
motor 2
P12.28
Power display
Description
0.01–655.35mH
0.01–655.35mH
0–10000V
0–0xFFFF
0%–50% (of the rated current of the motor)
0: No protection
1: Common motor (with low-speed compensation)
2: Frequency-variable motor (without low-speed
compensation)
Motor overload multiples M = Iout/(In×K)
In is rated motor current, lout is VFD output
current, K is motor overload protection coefficient.
The smaller the K, the larger the value of M, the
easier the protection.
if M is 116%, protection will be applied when motor
overloads for 1h; if M is 200%, protection will be
applied when motor overloads for 60s; if M is no
less than 400%, protection will be applied
immediately.
Time t
1h
1min
116 %
Setting range: 20.0%–120.0%
0.00–3.00
-198-
Motor overload multiples
200 %
Function parameter list
Default
Modify
value
Depends
○
on model
Depends
○
on model
○
300
●
0x0000
●
10%
◎
2
○
100.0%
○
1.00
Need help?
Do you have a question about the Goodrive350 Series and is the answer not in the manual?
Questions and answers