Goodrive350 series high-performance multifunction VFD
Function
Name
code
switch-on delay
Relay RO10
P26.34
switch-off delay
AO2 output
P26.35
selection
AO3 output
P26.36
selection
P26.37
Reserved
Lower limit of
P26.38
AO2 output
Corresponding
P26.39
AO2 output of
lower limit
Upper limit of
P26.40
AO2 output
Corresponding
P26.41
AO2 output of
upper limit
AO2 output filter
P26.42
time
Lower limit of
P26.43
AO3 output
Corresponding
P26.44
AO3 output of
lower limit
Upper limit of
P26.45
AO3 output
Corresponding
P26.46
AO3 output of
upper limit
AO3 output filter
P26.47
time
P26.48–
Reserved
P26.52
Description
The same with P06.14
Above function codes define the relation between
output value and analog output. When the output
value exceeds the set max./min. output range, the
upper/low limit of output will be adopted during
calculation.
When analog output is current output, 1mA
corresponds to 0.5V voltage. In different
applications, 100% of output value corresponds to
different analog outputs.
10V (20mA)
AO
0.0%
Setting range of P26.38: -300.0%–P26.40
Setting range of P26.39: 0.00V–10.00V
Setting range of P26.40: P26.38–100.0%
Setting range of P26.41: 0.00V–10.00V
Setting range of P26.42: 0.000s–10.000s
Setting range of P26.43: -300.0%–P26.45
Setting range of P26.44: 0.00V–10.00V
Setting range of P26.45: P26.43–300.0%
Setting range of P26.46: 0.00V–10.00V
Setting range of P26.47: 0.000s–10.000s
0–65535
-235-
Function parameter list
Default
value
0.000s
0
0
0
0.0%
0.00V
100.0%
10.00V
0.000s
0.0%
100.0%
0.00V
100.0%
10.00V
0.000s
0
Modify
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○