INVT Goodrive350 Series Operation Manual page 201

High-performance multifunction vfd
Hide thumbs Also See for Goodrive350 Series:
Table of Contents

Advertisement

Goodrive350 series high-performance multifunction VFD
Function parameter list
Function
Default
Name
Description
Modify
code
value
When the output current is detected to be lower
than the current-limit level again, it will continue
accelerated running.
Output current A
Current-limit
threshold
Time t
Output frequency f
Set
frequency
Constant
speed
Acceleration
Time t
Setting range of P11.06: 50.0–200.0%
Setting range of P11.07: 0.00–50.00Hz/s
0x000–0x1132
Ones place:
0: Motor overload/underload pre-alarm, relative to
rated motor current
1: VFD overload/underload pre-alarm, relative to
rated VFD current
Tens place:
0: The VFD continues running after
overload/underload alarm.
1: The VFD continues running after underload
VFD or motor
alarm, and stops running after overload fault.
P11.08
overload/underlo
0x000
2: The VFD continues running after overload
ad pre-alarm
alarm, and stops running after underload fault.
3: The VFD stops running after overload/underload
fault.
Hundreds place:
0: Always detect
1: Detect during constant-speed running
Thousands place: VFD overload current reference
selection
0: Related to current calibration coefficient
1: Irrelated to current calibration coefficient
-192-