Goodrive350 series high-performance multifunction VFD
Function
Name
code
Output torque
P08.22
calculation mode
Number of
P08.23
decimal points of
frequency
Number of
P08.24
decimal points of
linear speed
P08.25
Set count value P08.26–65535
Designated count
P08.26
value
P08.27
Set running time 0–65535min
Automatic fault
P08.28
reset times
Automatic fault
P08.29
reset time
interval
Reduction ratio of
P08.30
droop control
Switch-over
P08.31
between motor 1
and motor 2
Description
acceleration/deceleration only
0: Calculated based on torque current
0: Two decimal points
1: One decimal point
0: No decimal point
1: One
2: Two
3: Three
0–P08.25
Automatic fault reset times: When the VFD selects
automatic fault reset, it is used to set the times of
automatic reset, if the continuous reset times
exceeds the value set by P08.29, the VFD will
report fault and stop to wait for repair.
Interval of automatic fault reset: select the interval
time from when fault occurred to automatic fault
reset actions.
After VFD starts, if no fault occurred during 60s,
the fault reset times will be zeroed out.
Setting range of P08.28: 0–10
Setting range of P08.29: 0.1–3600.0s
This function code sets the variation rate of the
VFD output frequency based on the load; it is
mainly used in balancing the power when multiple
motors drive the same load.
Setting range: 0.00–50.00Hz
0x00–0x14
Ones: Switch-over channel
0: Switch over by terminal
1: Switch over by Modbus communication
2: Switch over by
PROFIBUS/CANopen/DeviceNet
3: Switch over by Ethernet communication
-177-
Function parameter list
Default
Modify
value
0
0
0
0
0
0min
0
1.0s
0.00Hz
0x00