Goodrive350 series high-performance multifunction VFD
Function
Name
code
during
overvoltage stall
Integral
coefficient of
P11.22
voltage regulator
during
overvoltage stall
Proportional
coefficient of
P11.23
current regulator
during
overvoltage stall
Integral
coefficient of
P11.24
current regulator
during
overvoltage stall
Enable VFD
P11.25
overload integral
P11.26
Reserved
VF vibration
P11.27
control method
Description
Setting range: 0–1000
This parameter is used to set the integral
coefficient of the bus voltage regulator during
overvoltage stall.
Setting range: 0–1000
This parameter is used to set the proportional
coefficient of the active current regulator during
overvoltage stall.
Setting range: 0–1000
This parameter is used to set the integral
coefficient of the active current regulator during
overvoltage stall.
Setting range: 0–2000
0: Disabled
1: Enabled
When this parameter is set to 0, the overload
timing value is reset to zero after the VFD is
stopped. In this case, the determination of VFD
overload takes more time, and therefore the
effective protection over the VFD is weakened.
When this parameter is set to 1, the overload
timing value is not reset, and the overload timing
value is accumulative. In this case, the
determination of VFD overload takes less time,
and therefore the protection over the VFD can be
performed more quickly.
0–65536
0x00–0x11
Ones place:
0: Method 1
1: Method 2
Tens place:
0: Reserved
1: Reserved
-195-
Function parameter list
Default
Modify
value
10
60
250
0
0
0x00