INVT Goodrive350 Series Operation Manual page 188

High-performance multifunction vfd
Hide thumbs Also See for Goodrive350 Series:
Table of Contents

Advertisement

Goodrive350 series high-performance multifunction VFD
Function
Name
code
Enable/disable
energy-
P08.37
consumption
brake
Energy-
consumption
P08.38
brake threshold
voltage
Running mode of
P08.39
cooling fan
P08.40
PWM selection
Description
Output frequency
Set
frequency
Y,
RO1, RO2
Setting range: 0.00Hz–P00.03 (Max. output
frequency)
0: Disable energy-consumption
1: Enable energy-consumption
Set the starting bus voltage of
energy-consumption brake, adjust this value
properly can brake the load effectively. The default
value will change with the change of voltage class.
Setting range: 200.0–2000.0V
0: Common running mode
1: The fan keeps running after power-on
2: Running mode 2
0x0000–0x1121
Ones place: PWM mode selection
0: PWM mode 1, 3PH modulation and 2PH
modulation
1: PWM mode 2, 3PH modulation
Tens place: PWM low-speed carrier limit
0: Low-speed carrier limit mode 1
1: Low-speed carrier limit mode 2
2: No limit
Hundreds place: Deadzone compensation method
0: Compensation method 1
-179-
Function parameter list
Detection amplitude
Time t
Time t
Default
Modify
value
1
220V
voltage:
380.0V;
380V
voltage:
700.0V;
660V
voltage:
1120.0V
0
0x1101