Generic Timer & Counter - ABB ACS880 Firmware Manual

Primary control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
Abs high
Both
Abs both
32.26
Supervision 3
action
No action
Warning
Fault
Fault if running
32.27
Supervision 3
signal
32.28
Supervision 3 filter
time
0.000 ... 30.000 s
32.29
Supervision 3 low
-21474830.00 ...
21474830.00
32.30
Supervision 3 high
-21474830.00 ...
21474830.00
33
33 Generic timer &
counter
33.01
Counter status
Bit
Name
0
On-time1
1
On-time2
2
Edge 1
3
Edge 2
4
Value 1
5
Value 2
6...15
Reserved
0000 0000b ...
0011 1111b
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Description
Action is taken whenever the absolute value of the signal rises
above its (absolute) upper limit.
Action is taken whenever the signal falls below its low limit or
rises above its high limit.
Action is taken whenever the absolute value of the signal falls
below its (absolute) low limit or rises above its (absolute) high
limit.
Selects the action the drive takes when the value monitored
by signal supervision 3 exceeds its limits.
Note: This parameter does not affect the status indicated by
32.01 Supervision
status.
No action taken.
A warning
(A8B2 Signal supervision
The drive trips on
80B2 Signal supervision
If running, the drive trips on
Selects the signal to be monitored by signal supervision
function 3.
For the available selections, see parameter
1
signal.
Defines a filter time constant for the signal monitored by signal
supervision 3.
Signal filter time.
Defines the lower limit for signal supervision 3.
Low limit.
Defines the upper limit for signal supervision 3.
Upper limit.
Configuration of maintenance timers/counters.
See also section
Maintenance timers and counters
Displays the maintenance timer/counter status word,
indicating which maintenance timers/counters have exceeded
their limits.
This parameter is read-only.
Description
1 = On-time timer 1 has reached its preset limit.
1 = On-time timer 2 has reached its preset limit.
1 = Signal edge counter 1 has reached its preset limit.
1 = Signal edge counter 2 has reached its preset limit.
1 = Value counter 1 has reached its preset limit.
1 = Value counter 2 has reached its preset limit.
Maintenance time/counter status word.
3) is generated.
3.
80B2 Signal supervision
3.
32.07 Supervision
(page 87).
Parameters 281
Def/FbEq16
4
5
6
No action
0
1
2
3
Zero
0.000 s
1000 = 1 s
0.00
-
0.00
-
-
1 = 1