133 Generic timer & counter
133.01
Counter status
Bit
Name
0
On-time1
1
On-time2
2
Edge 1
3
Edge 2
4
Value 1
5
Value 2
6...15
Reserved
0000h...FFFFh
133.10
On-time 1 actual
0 ... 4294967295 s
133.11
On-time 1 limit
0 ... 4294967295 s
133.12
On-time 1 function
Bit
Function
0
Counter mode
0 = Loop: If warning is enabled by bit 1, it stays active only for 10 seconds
1 = Saturate: If warning is enabled by bit 1, it stays active until reset
1
Warning enable
0 = Disable: No warning is given when the limit is reached
1 = Enable: A warning is given when the limit is reached
2...15
Reserved
0000h...FFFFh
133.13
On-time 1 source
False
True
RO1
Other [bit]
133.14
On-time 1 warning
select
On-time 1
Device clean
Description
Configuration of maintenance timers/counters.
See also section
Generic timers and counters
Displays the maintenance timer/counter status word,
indicating which maintenance timers/counters have
exceeded their limits.
This parameter is read-only.
Description
1 = On-time timer 1 has reached its preset limit.
1 = On-time timer 2 has reached its preset limit.
1 = Signal edge counter 1 has reached its preset limit.
1 = Signal edge counter 2 has reached its preset limit.
1 = Value counter 1 has reached its preset limit.
1 = Value counter 2 has reached its preset limit.
Maintenance time/counter status word.
Reading of on-time timer 1. Can be reset from the Drive
composer PC tool, or from the control panel by keeping
Reset depressed for over 3 seconds.
Reading of on-time timer 1.
Sets the warning limit for on-time timer 1.
Warning limit for on-time counter 1.
Configures on-time timer 1. This timer runs whenever the
signal selected by parameter
on.
After the limit set by
133.11 On-time 1 limit
warning specified by
133.14 On-time 1 warning select
given (if enabled by this parameter), and the timer resets.
The current value of the timer is readable from parameter
133.10 On-time 1
actual. Bit 0 of
indicates that the time has exceeded the limit.
On-time timer 1 configuration word.
Selects the signal to be monitored by on-time timer 1.
Constant 0.
Constant 1.
Bit 0 of
110.21 RO status
Source selection (see
Terms and abbreviations
13).
Selects the warning message for on-time timer 1.
Pre-selectable warning message for on-time timer 1.
Pre-selectable warning message for on-time timer 1.
(page 39).
133.13 On-time 1 source
is reached, the
133.01 Counter status
(page 60).
on page
Def/FbEq16
-
1 = 1
-
1 = 1 s
0 s
1 = 1 s
00b
is
is
1 = 1
False
0
1
2
-
On-time 1
0
6

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents