Object 605E
h
With the Fault reaction option code you can specify the reaction to the diagnosis that is to be exe-
cuted. The "Closed Loop Ramp" reaction is stored as standard.
Reset condition
Depending on the diagnostic message, reset conditions will be specified for eliminating the diagnostic
message. The following resets can be executed with the AX8000.
Diagnostic class / cause
Error: fatal hardware or software error
Error: fatal error
Error
Error due to motor replacement
Warning
Information
Possible causes
All causes that could have caused the diagnostic message are listed there. Please always read all of the
causes.
Solutions
Analogous to the causes, all solutions are listed there. The ordinal numbers before the "possible causes" and
the "solutions" correspond to one another.
Readout on the AX8000 display
Supply module
Display
E
P
P
Axis module
Display
A
A
Multi axis servo system - AX8000
– Fault reaction option code
Rest possible
No
Yes
Yes
Yes
Not required
Not required
Description
EtherCAT symbol flashes red
There is an EtherCAT error
Power symbol lights up red
There is a power supply error
Power symbol flashes red
There is a power supply error and the DC link is being charged or discharged
• Fast: DC link > 48 V
• Slowly: DC link ≤48 V
Description
Axis symbol is flashing red-green
Axis error reaction is active
Axis symbol is flashing red
There is an axis error
Introduction to the diagnostic system
Remedy
Replace servo drive if necessary
Restart AX8000
(interrupt 24 V power supply for at least 10 sec.)
Execute an NC error reset
Execute an NC error reset
There is no reaction by the AX8000 to any warning.
There is no direct reaction by the AX8000 to informa-
tion.
Version: 1.1
13